INSTALLATION & SERVICE MANUAL

TM

50 AMP Smart Energy Management System  Model 900

Next, looking across the other eight columns, find the one that matches the "Load Type" column you just filled in.  
Using the number at the top of the column, look in the table below to determine the settings of the three jumpers, JP2, JP3, 
and JP4.   A "Y" (for yes) means the jumper should be installed and an "N" (for no) means there should not be a jumper 
installed.

At the bottom of each column is the Relay Shed Order.  This determines which relays will be used for each load.   The one 
at the top of the column is first to be shed.   The one below it will turn off next, and so forth.  The loads 

MUST

   be wired in this 

order for the system to operate as desired.

Finally, the number and size of the circuit breakers should be selected to meet the needs of the installation.  The breakers 
can be either single or dual types.   Two of these breakers MUST be 50 Amp units to act as the Main breakers.  The 
breakers must be obtained and then installed in the box.  

(See information on breaker types later in this manual.)

COLUMN
NUMBER

RELAY

SHED

ORDER

(Top is

First Shed)

Содержание 00-00684-000

Страница 1: ...NAGEMENT EQUIPMENT MODEL900 50 AMP SERVICE by MADE IN THE U S A Intellitec 6 M A I N M A I N 1 1 4L54 R LISTED US C 50 Amp EMS Distribution Panel P N 00 00767 000 CAUTION TM The 50 AMP SMARTEMS Model...

Страница 2: ...is available the control helps to limit the total current draw of all the appliances in the RV at or below 30 20 Amps provided by the main power feed If the Generator source is available the control...

Страница 3: ...takes priority over all other modes that is if the generator is running the EMS will operate in that mode independent of the presence of other sources If 120 VAC is present at the L1 and L2 inputs an...

Страница 4: ...ictured adaptor is used on the incoming service press the service select button to select the 20 Amp mode Momentarily pressing this button again will switch the system back to the 30Amp mode The Displ...

Страница 5: ...rol loads based on a 60 Amp current rating for a diesel powered generator These jumpers are all installed at the factory Removing JP2 JP3 or JP4 will alter the order of shedding to suit the particular...

Страница 6: ...ans there should not be a jumper installed At the bottom of each column is the Relay Shed Order This determines which relays will be used for each load The one at the top of the column is first to be...

Страница 7: ...n the lower center of the box and secured with an appropriate connector The LINE 1 and LINE 2 supply mains should be connected to the corresponding main breaker The main ground lead should be connecte...

Страница 8: ...beled NEUTRAL See box drawing page 15 TM NOTE To insure proper operation of the source sensing circuitry on the 50AMP EMS Model 900 jumper wires must always be connected from a line 1 breaker to J6 te...

Страница 9: ...wired in series with the compressor control lead This means that the compressor control wire is cut and the two ends are wired to the Common and the Normally Closed contacts of Relay 5 or 6 In this w...

Страница 10: ...reverse direction The Display Panel should be plugged onto the harness observing the polarity as before The panel should then be installed in the hole and screwed in place using two 6 flat head screw...

Страница 11: ...hould show the amount of current that load is drawn Turn that appliance off and repeat this with each of the others To test the load shedding turn on all the controlled appliances The total current dr...

Страница 12: ...3041 Pin Function 1 Power 2 Data 3 Ground 4 30 20 Amp Select Line J6 5 Position Terminal Block Term Function 1 From Circuit Breaker for Relay 2 Must be connected to a LINE 2 Breaker 2 Output of Relay...

Страница 13: ...NOT the same as the incoming line repair the change over Refer to the change over service literature for trouble shooting II 120 volts available at non controlled appliances and receptacles Controlle...

Страница 14: ...the units to fail VIII Remote Display does not indicate GEN SET service source when generator is running Check wiring between generator run light circuit and J2 pin 2 on EMS Control Module J2 pin 2 s...

Страница 15: ...r 120 240 VOLT SIDE BRKR 4 RELAY 4 BRKR 3 RELAY 3 EMS Controlled Loads 1HP 15A 1 2 0VA C 60 H Z ENERGY MANAGEMENT CONTROL ELECTRONICS BARRIER RELAY 5 N O RELAY 5 COM RELAY 5 N C RELAY 6 COM RELAY 6 N...

Страница 16: ...senhower Lane North Lombard IL 60148 630 268 0010 1 800 251 2408 P N 53 00684 200 Rev A 071301 www Intellitecsve com Intellitec INSTALLATION SERVICE MANUAL TM 50 AMP Smart Energy Management System Mod...

Отзывы: