Intel® Server System S9200WK Product Family Setup and Service Guide
56
4.13
System Fan Replacement
The Intel® Server System S9200WK product family supports two system fan configurations, one for Liquid
Cooled configurations and one for Air Cooled configurations, as shown in the following illustrations.
Figure 61. System Fan Configuration - Liquid cooled system
Figure 62. System Fan Configuration - Air cooled system
The system is designed to support fan redundancy. Should a single fan rotor fail, system management will
engage various system thermal controls to maintain system thermals below maximum limits. Depending on
the system configuration, the system fans are designed to be hot swappable.
In air cooled configurations, the two outer 80mm system fans are hot swappable.
In liquid cooled and air cooled system configurations, three 60mm system fans share the same assembly
housing as a power supply module. The power supply module must be removed from the fan assembly
before removing the assembly housing from the chassis. Hot swapping these system fans can only be
supported when the system is configured to support 2 + 1 power supply redundancy. Attempting to hot
swap one of these fans with power redundancy lost will cause the entire system to shut down unless the
failed fan is in the same assembly as a failed power supply.