Emergency Operation

 

The emergency battens can be operated in maintained or non-maintained mode.
1.  The luminaire delivers 230 lumens in Emergency mode.
2.  Ensure the emergency battery is connected to the connector on the emergency driver.
3.  Ensure the status LED and manual test button connector are connected to the emergency driver.
For maintained operation:
•  Connect the Live cable (Brown) to terminal (L).
•  Connect the Switch Live cable to terminal (L1).
For non-maintained operation:
•  Connect the Live cable (Brown) to terminal (L).
•  Leave terminal (L1) disconnected.
4.  When powered on, the green LED indicator will illuminate indicating that the battery is being charged.
5.   To check that the emergency function is working, press the red test button at any time and the batten should illuminate in emergency mode.
6.   On failure of the permanent mains supply the fitting will switch automatically from battery charging to battery discharge powering the 

LED batten.

7.   This luminaire is designed to provide 3hrs of emergency light following a power failure. Please allow a full 24 hour charge before 

carrying a 3 hour test and mark the installation date on the LED batten label.

8.  This luminaire contains a 6.4V V 1500mAh Li-ion battery. For replacement please contact Integral-LED.com
9.  Please find Testing Schedule log at the end of this installation guide.

Sensor Operation

 

Lightspan battens are fitted with an optional sensor, this turns the batten on when the light level reaches the specified level.  Settings are 

made by setting dip switches on the sensor which is located inside the body of the fitting, please open the fittings as per the instructions 

above and set the dip switches in line with the table below, thank you.

Features:

•  On-Off function 
•  Stand-by power ≤ 0.5W 
•  Slim design
•  Small sensor head can reduce the shadow of the light 
•  Detection area, hold time and daylight threshold can be precisely set by DIP switch 

Sensor Specification

Input

Input Voltage

198-264V AC 50Hz

Rated Input Voltage

220-240V AC 50Hz

Stand-by Power

≤ 0.5W

Output

Load Power

250W (Inductive) 500W Resistive)

Hold Time

5s/30s/90s/3min/20min/30min

Sensor Parameters

Sensing Range

100%/75%/50%/25%

Daylight Sensor

Disable/50Lux/30Lux/10Lux/2Lux

Mounting Height

Ceiling Mounting:3-6m

Detection Area

Walking 0.5-1m/s keep walking≥2m walk & stop≥5m

Wireless Parameters

Operating frequency

5.8 GHz ±75 MHz

Dimming control

0N/0FF

Operating temperature

-25°C - +60°C

Operating Environment

Safety & EMC

EN55015

Certificate requirement

EMC TUV

Wiring method

Push terminal (4)

Others

IP rating

IP20(Built-in)

Protection Class

Class II

Installation Size

168*21*28mm

Packaging requirement

ClaOuter Carton (K=A)

Life

50000h