18: Output A voltage calibration
Interface
Setting
Parameter 2:
it always shows
OP.V
as output voltage.
Parameter 3:
it shows the internal measurement value of the output A voltage, and you
can calibrate it by pressing
Up
or
Down
according to the measurement from an external
voltage meter. The calibration result will be effective by pressing
Enter
. The calibration
range is limited /-9V. This function is normally used for parallel operation.
19: Output B voltage calibration
Interface
Setting
Parameter 2:
it always shows
OP.V
as output voltage*.
Parameter 3:
it shows the internal measurement value of the output B voltage, and you
can calibrate it by pressing
Up
or
Down
according to the measurement from an external
voltage meter. The calibration result will be effective by pressing
Enter
. The calibration
range is limited /-9V. This function is normally used for parallel operation.
*It will display number 1 under
to represent the output B voltage.
20: Output C voltage calibration
Interface
Setting
Parameter 2:
it always shows
OP.V
as output voltage.
Parameter 3:
it shows the internal measurement value of the output C voltage, and you
can calibrate it by pressing
Up
or
Down
according to the measurement from an external
voltage meter. The calibration result will be effective by pressing
Enter
. The calibration
range is limited /-9V. This function is normally used for parallel operation.
*It will display number 2 under
to represent the output C voltage.