USER MANUAL - LBU-ONL 1.5K/2.25K/3K/4.5K
VER.2211.17-One (ENG)
13
7.
INVERTER CONFIGURATION
Configuration menu allows setting of functions and parameters of the Inverter.
Menu is activated by pressing
< SELECT >
during 5 seconds with Inverter in STAND-BY or BYPASS mode (powered but without
activation of ON button).
To come back to normal state, ESC (00) screen can be selected to confirm with ENTER or simply user can wait 10 seconds to allow
Inverter to come back automatically.
In configuration mode, LCD displays ID of the menu and values of 2 adjustable parameters:
( 1 )
: MENU ID
( 2 )
: Function name
( 3 )
: Configurable value
KEYBOARD IN CONFIGURATION MODE:
<ON / MUTE>
Used as
key to navigate or changing parameters value
<OFF / ENTER>
Used as <
ENTER
> key to confirm modifications
<SELECT>
Used as
key to navigate or changing parameters value
CONFIGURATION MENU:
For this model, configuration menu has the options and functions listed below:
00
ESC:
To quit from configuration mode.
01
OUTPUT VOLTAGE:
- For 220V/230V models: Operator can select between: 208Vac / 220Vac / 230Vac /
240Vac. Factory set to: 230V
- For 120V models: Operator can select between: 110Vac / 115Vac / 120Vac /
127Vac. Factory set: 120V
02
CF: ENABLE / DISABLE FREQUENCY CONVERTER FUNCTION:
CF can be enabled or disabled according to the value selected in PAR 03:
ENA = ENABLE
DIS = DISABLE
If CF is enabled Function 03 must be set to preferred frequency value: 50Hz or 60Hz
This function allows Inverter to generate output at selected frequency no matter value
of input frequency