Connect to External Battery Bank 

If additional runtime is required connect Heat Master to external battery pack. 

 WARNING!!!!: 

Battery connection does not accept reverse polarity. 

 

Left terminal (+) in Heat Master must be connected to left terminal (+) in Ext. Battery 

 

Right terminal (-) in Heat Master must be connected to right terminal (-) in Ext. Battery 
 

 

     

 

Chart 1 

Chart 2 

 

5. Trouble Shooting 

Problem 

Possible Cause 

Solutions 

HEAT MASTER cannot be turned on 
after pressing the power switch. 

Low battery. 

Charge at least 4-6 hours. 

Battery defect. 

Replace the battery with the same type 

LCD flashes and alarm beeps 

continuously when utility power is 
normal. 

The HEAT MASTER is overload. 

Remove some loads first. Before 

reconnecting equipment, please verify 
that the load matches capacity 
specified in the specs. 

Circuit breaker trip. 

Reset the breaker. 

Battery defect. 

Replace the battery with the same type 
of battery. 

When power fails, back-up time is 
shorten. 

It is overload. 

Remove some critical load. 

Battery voltage is too low. 

Charge it at least 4-6 hours. 

Battery defect. It might be due to 
high temperature operation 
environment, or improper operation 

to battery. 

Replace the battery with the same type 
of battery. 

The mains is normal but it is battery 
mode. 

Power cord is loose. 

Reconnect the power cord properly. 

 

6. Specifications 

HEAT MASTER

Rated Output Capacity / Capacidad Nominal
Peak Capacity / Capacidad Pico

800 VA / 640 W (< 6 s)

Input - Entrada

Voltage / Voltaje - Frequency / Frecuencia

Output - Salida

Voltage / Voltaje - Frequency / Frecuencia
Auto-restart / Auto-arranque

Yes   /    Si

Internal Batteries - Baterías Internas

Type / Tipo

Backup Time / Autonomía (*)

Heater Mode:

Domestic hot water 

"ON" (80W)

Central heating 

circuit "ON" (120W)

    Heat Master:

75min

60min

    Heat  1 EXBATT:

260min

180min

Recharge Time / Tiempo de Recarga

Protections / Protecciones

Overloads / Sobre-Cargas
Surge/Spikes Protection / Protección contra Picos

Product Features / Características del Producto

Power Outlets / Tomas
Product Size-Weight / Dimensiones-Peso Producto
Operating / Condiciones de Operación

(*) Backup tests based on gas boiler: "ROCA SARA 24/24" dual domestic hot water & central heating functions (20.700Kcal/h ; 24KW max.)
(*) Autonomía con una caldera ROCA SARA 24/24 en modo de agua caliente y calefacción central (20.700Kcal/h ; 24KW max.)

MOV protection L-N / Protección MOV entre L-N

1 x FRENCH   or   1 x SCHUKO (CEE 7/4)   

319 x 190 x 150    -    (9 Kg)

 < 95% RH (non condensing)    /   < 40 dB    /   0-40ºC

Technical specs can be modified to comply with special project requirements / Las especificaciones se pueden ajustar para proyectos.
Specifications may change without further notice / Las especificaciones pueden cambiar sin previo aviso.

250 VA / 200 W

230V (162-268 Vac)  -  50Hz

230V (+/- 10'%)  -  50Hz

Maintenance Free VRLA-AGM   / Sellada Sin Mantenimiento

4-6 hours to 90% capacity / 4-6 Horas hasta 90%

Circuit Breaker with Manual Reset / Disyuntor Rearmable

 

 