Setting Up
CI-3K50601 Project 2191 DMR2731 Rev.1 18-08-11
17
15.
Press
to confirm your selection. The SET indicator will appear
and the display will stop flashing.
16.
Press
to exit Pulse Width setting routine. SET will disappear
and the
and
keys can be used to select a different Relay
parameter.
4.10 Energy Units and 1% Limit
Use this option to set the displayed energy units multiplier and to set a 1% limit on measured
energy on or off.
The unit multiplier can be set to Wh/VArh (x1), kWh/kVArh (kilo) or MWh/MVArh (Mega).
To prevent noise from being recorded and causing ‘meter creep’, a 1% limit can be imposed on the
measured input such that energy readings less than 1% of maximum are not recorded. This limit
can be turned off so that even small energy increments are recorded.
1.
Use the
(up) and
(down) keys to select the Energy
screen.
2.
Press
to select the Energy menu.
At this stage, you can use the
and
keys to select either the
Energy Units
or
1%
Limit
menu.
Energy Units
3.
With the Unit screen selected, press
to enter the Units
setting routine. The currently selected unit flashes.
4.
Use the
(up) and
(down) keys to select the required
units: x1, kilo or Mega.
5.
Press
to confirm your selection. SET will appear and the
display will stop flashing.