5.    PARAMETER LIST 
 

Mark

F0

— (Hysteresis) the difference between the set temperature and the control point temperature. 

 

 

 

 

The range:0~15

and the default is 2


Mark

F1

-(

K1 Delay

after the relay gets the power, it delays the time of both the opening and   

 

 

 

 

closing. The range: 0~+9minutes

and the default is 2 minutes. 

 

Mark

F2

—Set the lowest working control temperature

-40-0

and the default is -35

the lowest 

 

 

 

 

working temperature point

 

 
Mark

F3

—Set the highest working control temperature

1~+60

and the default is 60

the highest 

 

 

 

 

working temperature point

 

 
Mark

F4

Output control mode F4=1 Cooling Control, F4=2 Heating Control, F4 =3 Defrost Control, 

 

 

 

 

and the default is 1. 

 

Mark

F5

Calibration adjustment of actual temperature of probe. The range is 

-

5

--5

. The default is 

   

0. 

 
Mark

F6

—Defrosting cycle. The range: 0-24hours. The default is 6 hours. 

 

Mark

F7

—Defrosting time.The range

1-60minutes. The default is 20 minutes. 

 
Mark

F8

—Time constant of filtering input signal. The range

0-60sec The default is 6   

 
Mark

F9

—Reset to factory Option. select”1” for reset to defaults. select “2” Parameter is unchanged. 

 
Mark

Ed

 exit the program parameter setting 

The customers can make relative adjustments of the above parameters according to their demands. 
 

6.

INSTALLATION AND MOUNTING 

Instruments shall be mounted on vertical panel, in a 71x29 mm hole, and fixed using the special 

bracket supplied. To obtain an IP54 protection grade use the front panel rubber gasket (mod. RG-C) as 
shown in fig.3. 

The temperature range allowed for correct operation is 0

60 °C. Avoid places subject to strong 

vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes. Let air 
circulate by the cooling holes. 