C1210 MANUAL 

 

1. Warning 
1.1 Please read before using this manual     

This manual is part of the product and should be kept near the instrument for easy and quick reference. 
The instrument shall not be used for purposes different from those described hereunder. It cannot be 

used as a safety device. 

Check the application limits before proceeding. 

1.2 SAFETY PRECAUTIONS 

1. Check the supply voltage is correct before connecting the instrument. 
2. Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden 

temperature changes with high atmospheric humidity to prevent formation of condensation 

3. Warning: disconnect all electrical connections before any kind of maintenance. 
4. Fit the probe where it is not accessible by the End User. The instrument must not be opened. 
5. Consider the maximum current which can be applied to each relay (see Technical Data). 
6. Ensure that the wires for probes, loads and the power supply are separated and far enough from 

each other, without crossing or intertwining. 

2. GENERAL DESCRIPTION

 

Model C1210 is a microprocessor based controller suitable for applications on commercial temperature 

refrigerating units. It’s provided with 1 relay output to control a compressor. It’s also provided with 1 x NTC 
probe input for temperature control. 
The output relay is able to be manually activated with a press of the 

“SET” Button

 

3.    CONTROLLING LOADS 
3.1 THE TEMPERATURE CONTROL

 

F4 = 1 :When the temperature of the sensor is higher than the total value of the temperature set point 

and temperature difference (F0), the compressor time delay (F1) starts, the compressor starts and K1 is on. 
When  it  is  lower  than  the  value  that  the  control  temperature  minus  the  temperature  difference  (F0),  the 
compressor stops and K1 is off. 

 

 

Fig.1 

F4 = 2 :When the temperature of the sensor is lower than the value of the temperature set point minus 

the temperature difference (F0) , the time delay (F1) starts,K1 will then turn on. When the temperature of 
sensor is higher than the temperature set point and temperature difference (F0),      K1 will turn off. 

F4 = 3 : After working for a whole defrosting cycle (F6), it automatically enters the defrosting state, the 

compressor  stops,  and  the  cooling  indicator  goes  out.  And,  when  the  defrosting  time  reaches  F7,  the 
compressor starts. 

3.2    SPECIAL WORKING MODE: 

When  the  sensor  temperature  surpasses  the  highest  working  temperature  (F3)  or  the  sensor 

short-circuit 

shows “H1” (H2), or when the sensor temperature is below the lowest working temperature (F2) 

or the opening circuit of the sensor shows “L1” (L2), it enters the fixed time working mode. The compressor 
operates for 45 minutes and stops for 15 minutes.   

 