background image

                                                           

HWHC2100 v2.53 Operation Manual     

CONFIDENTIAL

 

 

 

 

21 Harbor Park Dr. N, Port Washington, NY 11050 Phone: 516.626.72211 Fax: 516.626.7201 

 

7. Operation Parameters 

 

 
To provide correct and reliable operation of the HWHC2100 the operational parameters must be set properly. 

The parameter section of the menu is divided in two parts (MAINTENANCE and SETUP). Each part protected with a 
password. Use following tables as guidelines when selecting parameters' values: 
 
 
 
 

MAINTENANCE

 

(password:CACADCB) 

 

Parameter 

Description 

Heat Gain 

Determines ratio between the System Hot Water Temperature and Outdoor Temperature.  

Fig. 3a,b represents the family of control curves with different Heat Gain as parameter when Mild Weather is 
70°F  (Fig.3a) and Mild Weather is 55°F (Fig.3b). With any of the ratios, the colder it becomes outside, the hotter 
the temperature of the system water. On the both examples Compensator=0 and NIGHT SETBACK=0. 

Positive Compensator values shift the curve up, negative - down. 

Positive Night Setback values shift the curve down. 

Positive Compensator values shift the curve up, negative - down. 

Positive Night Setback values shift the curve down. 

Implemented 10 different ratios: 

1:3; 1:2; 1:1.5; 1:1.25; 1:1; 1.25:1; 1.5:1; 2:1; 3:1; 4:1.

 

Ratio 4:1

 (OD : ST)  - the outdoor temperature would have to drop 4° to increase the system water temperature 

by 1 degree. 

Ratio 1:3

 (OD : ST)  - for each 1 degree drop in  outdoor temperature  the hot water temperature will increase by 

3 degree. 

Default ratio

 

is 1:1;

 

Fig.3a  Heat Gain 
Ratio (Mild 
Weather is 70°F  ) 
curves. 

 

70

100

130

160

190

220

250

-20

-10

0

10

20

30

40

50

60

70

Outdoor Temperature (in F)

S

y

s

te

m

 W

a

te

T

e

m

p

e

ra

tu

re

 (

in

 F

)

1:3

1:2

1:1.5

1:1.25

1:1

1.25:1

1.5:1

2:1

3:1

4:1

 

Содержание HWHC2100

Страница 1: ...temperature or condensate return temperature return water temperature HWHC2100 works as a standalone controller and can be connected to a Local Server which provides additional parameters adjustments...

Страница 2: ...es or change settings The control keypad consists of four pushbuttons Escape Esc Down Up Enter Enter The keys are also marked with letters A B C D used to simplify the passwords memorizing During norm...

Страница 3: ...ened or closed depending on the mode of the last operation as follows Operation Mode Valve Direction Status Information AUTO To Close Position Sync_C M_SET To Close Position Sync_C M_CLOSE To Close Po...

Страница 4: ...d then one should enter a certain key sequence For convenience the passwords are coded as the sequence of letters e g DDBBCBA Starting point of the menu is the topmost item of the leftmost box current...

Страница 5: ...s SET TIME DATE SET Minute NEWMinute 56 VlvCtlType Curnt SET Com ID NEW Com ID 3 SET Hour NEW Hour 2PM D Mild 55 F CACADCB SET Month NEW Month 02 N Mild 45 F SET MAINTENANCE Password1 SET D Mild NEW D...

Страница 6: ...h between the different configuration one should press Up or Down keys Hitting Enter key accepts the new configuration Esc rejects and leaves the configuration unchanged 6 Modes of operation The upper...

Страница 7: ...he NIGHT MILD WEATHER and NIGHT SETBACK parameters Please see an example in section 6 Notes The valve will be unconditionally set to 0 when Out Door Temperature achieves Day time Mild Weather Set Poin...

Страница 8: ...Fig 3b With any of the ratios the colder it becomes outside the hotter the temperature of the system water On the both examples Compensator 0 and NIGHT SETBACK 0 Positive Compensator values shift the...

Страница 9: ...g 4 illustrates effects of the Compensator on the control curve Range 40 F to 40 F with 1 step Default value is 0 F D Mild DAY MILD WEATHER The controller closes the valve completely when the outdoor...

Страница 10: ...ens 10 Boost Span Morning boost time span The controller boosts heat only with AUTO mode in effect Range 0 30 60 90 120 minutes 0 means no boost or Vari Boost the length of the Boost time depends on t...

Страница 11: ...d from host computer is higher than this set point and the time is between Day End and Day Begin then the valve will be closed completely N ICOFF state Range 40 to 80 F InDrD_Band Used along with In D...

Страница 12: ...de of operation specify the appropriate time in seconds between the Valve Motor motion Normally this parameter is set at the system installation time Range 0 to 127 seconds with 1 second step Default...

Страница 13: ...ration Valve position is 37 open System temperature is 144 F Morning Heat Up Calculated Target Temperature is 188 F AUTO 189 BOOST AUTO 140 D Mild AUTO 140 N Mild VLV 37 ST 155 VLV 12 ST 144 VLV_0 ST...

Страница 14: ...ign will change to Mode of Operation OFF Mode of Operation M_SET SET 180 VLV 67 ST 123 Target Temperature is 180F Normal operation system temperature is 123F For the motorized valve controlled by rela...

Страница 15: ...adjustment valve position would perform at the close position Pump would be turn off after period of time set by the Pump Run On set point System Temperature Sensor fails Initial Synchronization Valv...

Страница 16: ...and shows actual reading of the temperature sensor ST zz x 3 The lower line of the display shows possible adjustment for example NewSysTAdj 0 2 4 Press Up or Down key to make the reading equal to the...

Страница 17: ...MCI Transformer 4 06 7345 1 5 10 9 7 6 Pump1 2 Pump1 1 Pump2 1 Pump2 2 9 5 12 4 8 13 14 Terminals Board J1 1 2 3 H H 8 9 10 11 12 13 14 7 4 5 6 1 2 J2 1 2 Transformer 1 9 5 4 8 9 5 Motor Controls comm...

Отзывы: