HWHC-2100 Operation Manual   

CONFIDENTIAL

 

 

 

 

21 Harbor Park Dr. N, Port Washington, NY 11050 Phone: 516.626.72211 Fax: 516.626.7201 

Hot Water Heating Controller 

 

Hot Water Heating

 

Controller HWHC2100  

 

Operation Manual 

 

1. Introduction 

 

 

The  Hot  Water  Heating  Controller  HWHC2100  (Fig  1)  provides  control  of  the  Building's  mixing  valve,  heat 

exchange  valve  or  the  burner  operations  to  regulate  the  heating  water  temperature  or  the  amount  of  thermal  energy 
supplied  to  the  Building.  The  HWHC2100  adjusts  the  temperature  of  the  heating  water,  calculating  the  target 
temperature, in response to changes to the outdoor temperature.  The HWHC2100 controls the motorized valve and the 
circulation pumps. Alternatively, the control could be provided directly to the burner operations. 
            In  Auto  mode  the  HWHC2100  distributes  heat  energy  entering  in  the  building  in  accordance  with  weather, 
outdoor  temperature  and  installed  parameters.  Depending  on  the  controller’s  configuration  the  main  parameter  of  the 
regulation could be either the hot water in house input the supply temperature (system water temperature) or condensate 
return temperature (return water temperature).  
 

HWHC2100 works as a standalone controller and can be connected to a Local Server, which  provides  additional 

parameters adjustments to HWHC2100 based on apartment's indoor real time temperature. This feature will improve the 
heating supply and distribution efficiency and can eliminate the apartments over or under heating. When the HWHC2100 
is  connected  to  the  Local  Server  it  can  be  monitored  and  controlled  from  the  local  Intranet  and/or  Internet  with 
appropriate authentication. 

 

 

 

 

Fig1.  HWHC2100. Front view 

 
 

                                                          The HWHC2100 features: 

 

 

Configurable to controls the zone valve or boilers to regulate the circulated water temperature.  

 

Adaptable to different type of actuators: floating point, 4-20mA, 0– 5V, 0–10V or 135ohm input. 

 

Automatic positioning of the zone valve or adjusting the boilers stages in accordance with operation settings and 
measured temperatures. 

 

Manual Control Mode. 

 

Displays the valve position circulation pumps and/or boilers status. 

 

Day and Night modes of operation with programmable time durations. 

 

Programmable heating season dates. 

 

Flexible selection of the feedback control temperature source (system (supply) or return). 

 

Extended Heat-Up period up to 100 minutes with step of 1 min. 

HWHC2100 

Содержание HWHC2100

Страница 1: ...temperature or condensate return temperature return water temperature HWHC2100 works as a standalone controller and can be connected to a Local Server which provides additional parameters adjustments...

Страница 2: ...es or change settings The control keypad consists of four pushbuttons Escape Esc Down Up Enter Enter The keys are also marked with letters A B C D used to simplify the passwords memorizing During norm...

Страница 3: ...ened or closed depending on the mode of the last operation as follows Operation Mode Valve Direction Status Information AUTO To Close Position Sync_C M_SET To Close Position Sync_C M_CLOSE To Close Po...

Страница 4: ...d then one should enter a certain key sequence For convenience the passwords are coded as the sequence of letters e g DDBBCBA Starting point of the menu is the topmost item of the leftmost box current...

Страница 5: ...s SET TIME DATE SET Minute NEWMinute 56 VlvCtlType Curnt SET Com ID NEW Com ID 3 SET Hour NEW Hour 2PM D Mild 55 F CACADCB SET Month NEW Month 02 N Mild 45 F SET MAINTENANCE Password1 SET D Mild NEW D...

Страница 6: ...h between the different configuration one should press Up or Down keys Hitting Enter key accepts the new configuration Esc rejects and leaves the configuration unchanged 6 Modes of operation The upper...

Страница 7: ...he NIGHT MILD WEATHER and NIGHT SETBACK parameters Please see an example in section 6 Notes The valve will be unconditionally set to 0 when Out Door Temperature achieves Day time Mild Weather Set Poin...

Страница 8: ...Fig 3b With any of the ratios the colder it becomes outside the hotter the temperature of the system water On the both examples Compensator 0 and NIGHT SETBACK 0 Positive Compensator values shift the...

Страница 9: ...g 4 illustrates effects of the Compensator on the control curve Range 40 F to 40 F with 1 step Default value is 0 F D Mild DAY MILD WEATHER The controller closes the valve completely when the outdoor...

Страница 10: ...ens 10 Boost Span Morning boost time span The controller boosts heat only with AUTO mode in effect Range 0 30 60 90 120 minutes 0 means no boost or Vari Boost the length of the Boost time depends on t...

Страница 11: ...d from host computer is higher than this set point and the time is between Day End and Day Begin then the valve will be closed completely N ICOFF state Range 40 to 80 F InDrD_Band Used along with In D...

Страница 12: ...de of operation specify the appropriate time in seconds between the Valve Motor motion Normally this parameter is set at the system installation time Range 0 to 127 seconds with 1 second step Default...

Страница 13: ...ration Valve position is 37 open System temperature is 144 F Morning Heat Up Calculated Target Temperature is 188 F AUTO 189 BOOST AUTO 140 D Mild AUTO 140 N Mild VLV 37 ST 155 VLV 12 ST 144 VLV_0 ST...

Страница 14: ...ign will change to Mode of Operation OFF Mode of Operation M_SET SET 180 VLV 67 ST 123 Target Temperature is 180F Normal operation system temperature is 123F For the motorized valve controlled by rela...

Страница 15: ...adjustment valve position would perform at the close position Pump would be turn off after period of time set by the Pump Run On set point System Temperature Sensor fails Initial Synchronization Valv...

Страница 16: ...and shows actual reading of the temperature sensor ST zz x 3 The lower line of the display shows possible adjustment for example NewSysTAdj 0 2 4 Press Up or Down key to make the reading equal to the...

Страница 17: ...MCI Transformer 4 06 7345 1 5 10 9 7 6 Pump1 2 Pump1 1 Pump2 1 Pump2 2 9 5 12 4 8 13 14 Terminals Board J1 1 2 3 H H 8 9 10 11 12 13 14 7 4 5 6 1 2 J2 1 2 Transformer 1 9 5 4 8 9 5 Motor Controls comm...

Отзывы: