Intec SM-501 Series Скачать руководство пользователя страница 2

SM-501-N  4-Wire, Ionization Type 
SM-501-P  4-Wire, Photoelectric Type

INSTALLATION AND MAINTENANCE  INSTRUCTIONS 
FOR SM-501 SERIES DUCT SMOKE DETECTORS

PRODUCT OVERVIEW

PRODUCT APPLICATION

SM-501 Series duct smoke detectors provide early detection of smoke 
and products of combustion present in air moving through an HVAC 
duct supply, return, or both in commercial, industrial, and residential 

applications. These devices are designed to prevent the recirculation of 
smoke in areas by the air handling system’s fans, and blowers. Complete 
systems may be shut down in the event of smoke detection.

 

NOTE

: For the correct installation of a duct smoke unit, please refer to

the NFPA 72 (National Fire Alarm Code), NFPA 90A (Standard for Installation of 

Air Conditioning and Ventilation Systems),NFPA 92A (Recommended Practice for 

Smoke Control Systems.), NFPA 5000 (Building Construction and Safety Code),

IMC (International Mechanical Code), and IFC (International Fire Code).

This detector is not intended for open area protection nor should it be used for 

early warning detection or replace a regular fire detection system.

PRODUCT DESCRIPTION

The SM-501 Series smoke detector is fitted with a mounting base that will 
accept an ionization smoke detector head model 55000-225 (or 55000-
250) or photoelectric smoke detector head model 55000-328 (or 55000-
350).  The duct unit supports two sets of form “C” alarm contacts and one 
form “C” trouble contact. The trouble contact supervises the presence of 

the input power and removal of the detector head.  

 THE TROUBLE CONTACTS (TERMINALS 13-14, 15)

ARE SHOWN IN THE NON-ENERGIZED CONDITION. IN 

NORMAL OPERATION,CONTACTS WILL BE REVERSED.

The trouble contacts will not operate in the event of a smoke alarm. 

The SM-501 Series duct detector will operate from various input voltage 
sources; namely 24VAC, 24VDC, 115VAC and 230VAC.

SAMPLING TUBES

The operating principle of a duct detector is based on the Venturi effect. 

Two tubes extend into the HVAC duct. Air flowing through the duct is 
forced into the air intake (inlet) tube via the air intake holes, (facing the 
airflow) and passes over the detector head. The air will be drawn out 

via the exhaust tube back into the HVAC duct. (A 7” exhaust tube is 
provided in the installation kit.) When the concentration of smoke particles 
suspended in the air stream reach the alarm threshold of the detector 
head, the unit will go into alarm.

The duct smoke detector units are designed to operate in duct widths 
from 6” to 10’ wide with an air velocity between 500 to 4,000 feet per 

minute. To verify correct installation, the pressure differential between 
the sampling (high side) and exhaust (low side) tubes should be measured 
using a Magnehelic pressure gauge or equivalent. An acceptable reading is 
between 0.01 and 1.2 inches of water.

To minimize the impact of air turbulence and stratification on performance,
a duct smoke detector should be located as far as possible downstream 
from any obstruction (i.e. deflector plates, elbows, dampers, etc.). In 

all situations, confirmation of velocity and pressure differential within 
specifications is required.

REMOTE ACCESSORIES

Audible and visual alarm indicators, remote status indicators, and 
remote reset/test switches can be accommodated by the SM-501 Series 

duct units by connecting to DC voltage output terminals 16 through 
21. These terminals are not supervised and the voltage/current will
only be present when the detector unit is in alarm. The remote pilot 

(green) LED will be permanently illuminated when connected to the 
output terminals as long as input power and detector head are present.

 

SM-501 AT-A-GLANCE

MODEL NUMBER:  
SM-501-N    

4-Wire Ionization Duct Smoke Detector 

SM-501-P 

4-Wire Photoelectric Duct Smoke Detector

DETECTOR HEAD MODEL NUMBER:  
Ionization Detector Head:    55000-225
Photoelectric Detector Head:  55000-328

POWER REQUIREMENTS: 

STANDBY CURRENT  

ALARM          CURRENT

24VAC 35.0mA

24VAC

74.0mA

24VDC

15.0mA

24VDC

56.0mA

115VAC

25.0mA

115VAC

32.0mA

230VAC

12.0mA

230VAC

16.0mA

RELAY CONTACT RATINGS:
Alarm contacts: 

2 Sets form “C” rated at 10A @ 115VAC resistive 

Trouble contacts: 

1 Set form “C” rated at 10A @ 115VAC resistive  

Air velocity: 

500 to 4,000ft/min.

Ambient temperature: SM-501-N: 32°F to 158°F (0°C to 70°C)

SM-501-P: 32°F to 140°F (0°C to 60°C)

Humidity:  

10% to 85% RH Non-Condensing/Non-Freezing

Material: 

18GA steel back box, clear plastic cover 
(Makrolon 94V-0)

Finish: 

Gray paint on black box

Dimensions: 

9 1/8” L X 7 1/4” W X 2 1/4” H

Max. net wt.: 

3 1/2 lbs.

Radioactive element: SM-501-N (Ionization) - Americium 241, 

0.9 micro curie. 
Do not expose to corrosive atmospheres.

!

!

2 of 6

150303

Specifications subject to change without notice. | INST APD0191 D140113 | USA 150303 | Page 2 of 7

12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN

TEC

 | relevantsolutions.com/inteccontrols

SM-501 – Installation

Содержание SM-501 Series

Страница 1: ...ned in all this document should be considered before installing or using the product Any example applications shown are subject to the most current enforced local national codes standards approvals ce...

Страница 2: ...e air stream reach the alarm threshold of the detector head the unit will go into alarm The duct smoke detector units are designed to operate in duct widths from 6 to 10 wide with an air velocity betw...

Страница 3: ...10 0 For duct widths of 5 0 to 10 0 FAST TUBE Sectional Tube for duct widths up to 8 0 Standard sampling tubes are steel tubes with air intake holes drilled the entire length of the tube FAST Tubes ar...

Страница 4: ...A MAX 115VAC INPUT Terminals 1 2 3 230VAC 50 60 Hz 0 1A MAX 230VAC INPUT Terminals 1 2 4 24VDC OPERATION 115VAC OPERATION 230VAC OPERATION G H1 H2 24VAC OPERATION WIRING CAUTION For terminals 7 15 do...

Страница 5: ...tector X SM 501 Detector 1 11 15 12 INTERCONNECTION WIRING FOR COMMON FUNCTIONS MS REMOTE ACCESSORY WIRING C TB P C AL T R 18 20 21 17 19 14 JUMPER A jumper wire must be placed between Terminals 14 an...

Страница 6: ...e alarm relays will change state and the alarm related remote accessories if attached will function If no test gas is available to conduct functional testing light a piece of clothesline rope and blow...

Страница 7: ...itch MS RH P A Remote Alarm Pilot Horn MS RH KA P A T Remote Alarm Trouble Pilot Horn key operated Test Reset Switch MS RA P T Remote Pilot Trouble MS RA FT P Remote Pilot Trouble push button Test Res...

Отзывы: