SC2-AT6 – UserManual

3  Electrical Connection

3.1  Plug Connection (SC2)

SC2 sensors are equipped with a reverse polarity protected connector (3-pin). It mustn’t be plugged in the wrong 

position by force (already clamped at the factory).
All black plugs are connected in parallel, so it is irrelevant which plug to use.

3.2  Terminal Connection (AT6)

•  Open cover.

•  Insert field bus cable from above, cut and strip it.

•  Connect it to the terminal (only 3-wire connection possible).
•  For the 4-20 mA operating mode, please remove the built-in 

500 ohm resistor between terminals 2 and 3.

4  Commissioning

Only 

trained technicians

 should perform the following when commissioning:

•  Check for correct mounting location.
•  Check if connection is correct.
•  Check power voltage (for AT6).
•  Install the Sensor Cartridge(s) if not already installed ex works.
•  Check Sensor Cartridge connector for correct engagement.
•  Calibration; note that new sensors are pre-calibrated at the factory.

Within the first weeks after commissioning, there may be a deviation in the sensor behavior. Required instruments for 

commissioning (calibration):

•  Service Tool STL6 or
•  DPT6 kit (DGC6 EasyConf Software incl. USB/RS-485 adapter)
•  Calibration Gases:

•  For toxic and oxygen sensors 

•  Zero gas bottle with synthetic air (20% oxygen, 80% nitrogen) 

•  Span gas bottle of target gas in the range of 30-90% of the measuring range. Rest is synthetic air.

•  For combustible sensors 

•  Zero gas bottle with synthetic air (20% oxygen, 80% nitrogen) 

•  Span gas bottle of target gas in the range of 30-70% of the measuring range. Rest is synthetic air.

•  For infrared CO

2

 sensors 

•  Zero gas bottle with pure nitrogen 5.0 for zero-point calibration 

•  Span gas bottle with CO

2

 in the range of 30-90% of the measuring range. Rest is synthetic air.

•  Extraction set consisting of gas pressure regulator and flow meter

•  Calibration adapter with tube; CONKIT-PG2.

Sensor Unit

AT6

3 2 1

4-20 mA / 2-10 V

GND

+24 V

Содержание PolyGard 2 AT6

Страница 1: ...12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 888 GO INTEC inteccontrols com April 13 2020 Revision Toxic E Combustible P and Infrared I CO2 Gases PolyGard 2 SC2 AT6 Sensors User Manual...

Страница 2: ...missioning 6 4 1 Installation of Sensor Cartridge 7 4 2 Registration of the Sensor Cartridge 7 5 Calibration 7 5 1 Calibration Process 8 5 2 Exchange of Sensor Cartridge 9 6 Inspection and Service 9 6...

Страница 3: ...fic PG2 device 1 3 Special Mode See description on datasheet for the specific PG2 device 1 4 Sensor Element for Toxic Gases and Oxygen The sensor element is a sealed electro chemical cell with three e...

Страница 4: ...ne silicone Corrosive substances such as halogenated hydrocarbons Catalytic poisons such as sulphur and phosphor compounds silicon compounds metal vapours Organic solvents For testing the sensor do no...

Страница 5: ...1125 C Ammonia NH3 0 300 ppm 4 000 Ceiling E1125 D Ammonia NH3 0 1000 ppm 4 000 Ceiling E1193 C Chlorine Cl2 0 10 ppm Near Source Floor E1183 C Hydrogen Cyanide HCN 0 100 ppm Near Source Ceiling E1189...

Страница 6: ...tage for AT6 Install the Sensor Cartridge s if not already installed ex works Check Sensor Cartridge connector for correct engagement Calibration note that new sensors are pre calibrated at the factor...

Страница 7: ...ram is also available consult your account executive Prior to calibration the Sensor Cartridge must be supplied with power voltage without interruption for warm up and stabilization The warm up time d...

Страница 8: ...he buffer memory The current measured value is output with the new offset factor and the offset display is updated With Save the new offset factor is written in the SC memory only then the Zero calibr...

Страница 9: ...local bus communication has been re established and the conformity test has been successful the LED goes into flashing mode with 3 sec pulse duration until the sensor s warm up time is over Apply a de...

Страница 10: ...ads If this interval is exceeded a digital maintenance message is generated and forwarded Performing the calibration automatically deletes this message AT6 Sensor heads If this interval is exceeded th...

Страница 11: ...correct at X4 Connect correctly Connector X4 not plugged in Check the plug Wire breakage Check the wiring Green LED doesn t flash PCB no address Check PCB address address correctly PCB no field bus co...

Страница 12: ...e does not claim to be complete The indicated sensitivity data are only standard values referring to new sensor elements 9 Technical Data All specifications were collected under optimal test condition...

Страница 13: ...0 2 1 2 4 149 15 90 24 1 59 5 6 12 E1130 C NO2 0 30 0 5 0 1 2 25 0 2 1 2 4 149 15 90 24 1 59 5 6 12 E1130 D NO2 0 500 20 2 2 25 0 2 1 2 4 149 15 90 24 1 59 5 6 12 E1129 C NO 0 100 0 15 0 1 2 45 0 5 1...

Страница 14: ...A C4H8O2 0 100 1 0 2 1 15 0 5 0 3 1 4 122 5 95 36 3 04 Floor 6 P3425 A C2H5OH 0 100 1 0 2 1 15 0 5 0 3 1 4 122 5 95 36 1 59 Floor 6 P3410 A C2H4 0 100 1 0 2 1 15 0 5 0 3 1 4 122 5 95 36 0 98 Ceiling...

Страница 15: ...00 0 5000 0 10 12 10 30 20 0 20 0 1000 150 E1125 DX NH3 10 0 100 0 100 0 200 0 5000 0 10 12 10 30 20 0 20 0 1000 150 E1125 EX NH3 10 0 100 0 100 0 200 0 5000 0 10 12 10 30 20 0 20 0 1000 150 E1193 XX2...

Страница 16: ...change without notice Tox_D_1119 Ex_D_1119 CO2_D_0320 USA 200413 Page 16 of 17 SC2 AT6 UserManual 10 Figures Fig 1 Printed Circuit Board with Sensor Cartridge Mounting Mounting Mounting 115 mm X3 X2...

Страница 17: ...tential bonding required also e g secondary potential to earth or grounding measures must be carried out in accordance with the respective project requirements It is important to ensure that no ground...

Отзывы: