MGC2 – UserManual
PolyGard
®
is a registered trademark of MSR-Electronic GmbH
4.7.2 Current Value
Symbol
Description
Setting Status
Function
OFF
Current value
OFF
OFF = Current values of all registered SP are not recorded.
ON = Current values of all registered SP are recorded.
Release of the current value recording of all active sensor points on the USB device in a CSV file. The file name is
generated by the system and can’t therefore be determined manually.
The name of the file is structured as follows:
CVMMTT.csv, where MM represents the current month and TT the current day.
Every day, a new file with the current date is created. This makes sure that the files won’t be too big to be still edited by
established PC programs.
Internal structure of the file
(The headlines and column numbers are only for easy explanation and aren’t written in the file!)
Column 1
2
3
4
5
6
7
8
9
10
etc.
Time
SP1
SP2
SP3
SP4
SP5
SP6
SP7
SP8
SP9
SP10
09_50_02
0
20
20
28
0
-
0
0
0
09_50_03
0
20
20
28
0
-
25
29
0
09_50_04
0
20
20
28
0
-
25
29
0
09_50_05
0
20
20
28
0
-
25
29
0
09_50_06
0
20
20
28
0
-
25
29
0
09_50_07
0
20
20
28
0
-
25
29
0
09_50_08
0
20
20
28
0
-
25
29
0
09_50_09
0
20
20
28
0
-
25
29
0
09_50_10
0
20
20
28
0
-
25
29
0
09_50_11
0
20
20
28
0
-
25
29
0
09_50_12
0
20
20
28
0
-
0
29
0
The first column gives the time, from the second column on, the current values of all registered sensor points at this
time are written. Inactive sensor points within active sensor points are marked by a dash -.
Values here less than 0 stand for an error status of the sensor point.
- 50 = Sensor point locked.
- 40 = Communication error at the sensor point.
- 10 = Analog sensor points with a measured value less than 3 mA.
In this way the file keeps a fixed structure and can be evaluated with Excel and graphed according to the chronological
sequence.