5.3   Option Relay Output 

The  two  relays  are  activated  in  dependence  of  the  gas concentration.  If  the  gas  concentration  exceeds  the 

adjusted  alarm  threshold,  the  corresponding  relay  switches  on.  If  the  gas  concentration  falls  below  the 

threshold minus hysteresis, the relay switches off again. 
The contact function for relay 2, NC (normally closed) or NO (normally open), can be selected via the jumper 

NO/NC. See fig 1 and 3. Relay 1 is equipped with a change-over contact. 
Via the MODBus interface the two alarm thresholds and the hysteresis are freely adjustable at the PC within 

the measuring range. The procedure can be read from the user manual “MODBus Software”. 
The following parameters are factory-set. 
Alarm threshold 1 = Relay 1:   10 % LEL 
Alarm threshold 2 = Relay 2:   20 % LEL 
Switching hysteresis:      5 % LEL 

Specifications subject to change without notice. | USA 151203 | Page 8 of 14

12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN

TEC

 | relevantsolutions.com/inteccontrols

AT-3300_V3 – UserManual

Polygard® is a registered trademark of MSR | AT-3300_V3_UserManual

Содержание PolyGard AT-3300 V3

Страница 1: ...inted in USA 150313 March 13 2015 Revision Polygard is a registered trademark of MSR AT 3300_V3_UserManual PolyGard AT 3300 V3 Transmitter for Combustible Gases Serial No ET03 002 User Manual April 20...

Страница 2: ...y data AT 34XX V3 7 5 3 Option Relay Output 8 6 Inspection and Service 9 6 1 Inspections 9 6 2 Calibration 9 6 3 Exchange of Sensor Element 9 7 Troubleshooting 9 7 1 Analog Mode 9 8 Technical Data 10...

Страница 3: ...s voltage signal 0 2 10 V 2 2 Sensor The integrated sensor works according to the catalytic bead principle The ambient air being monitored diffuses through a sintered metal disk into the sensor Here t...

Страница 4: ...rs with a density air the transmitter must be located at the highest point possible Gas density and mounting height can be read from the table Cross sensitivity data Choose mounting location of the se...

Страница 5: ...for proper mounting at X4 and X5 Check the sensor for proper mounting at the connectors X8 of the PCB AT 33XX V3 only AT 34XX V3 Calibrate the transmitter if not already factory calibrated Required in...

Страница 6: ...sor for correct mounting 5 1 2 Gain Connect calibration adapter carefully to the sensor element Apply calibration test gas 150 ml min 1 Bar 14 5 psi 10 Wait two minutes until the signal is stable adju...

Страница 7: ...Benzene C6H6 44 1 30 2 70 Floor Cyclohexane C6H12 44 1 30 2 91 Floor Ethylene CH2 81 2 30 0 98 Ceiling Ethane C2H6 82 3 00 1 05 Floor Ethyl Alcohol C2H5OH 75 3 30 1 59 Floor Ethyl Acetate CH3COOC2H5 4...

Страница 8: ...3 Relay 1 is equipped with a change over contact Via the MODBus interface the two alarm thresholds and the hysteresis are freely adjustable at the PC within the measuring range The procedure can be re...

Страница 9: ...the sensor element into the PCB ET03 at XB7 XB8 Replug the PCB AT 33XX V3 into terminal blocks X4 X5 carefully Calibrate according to section 5 7 Troubleshooting 7 1 Analog Mode Trouble Cause Solution...

Страница 10: ...e polarity protected Power consumption without options 35 mA max 0 85 VA Output signal Analog output signal Selectable Current tension Starting point 0 20 0 4 20 mA load 500 0 2 10 V load 50 k proport...

Страница 11: ...ng Temperature controlled 3 C 2 C 37 5 F 3 6 F Ambient temperature 30 C 22 F Power supply 18 28 VDC AC Power consumption 0 3 A 7 5 VA Indications only for option stainless steel for further types see...

Страница 12: ...NO NC XA3 1 XA3 2 Gain ET03_001 0 20 Test Bridge Connector Service Tool R1 X5 Zero Option Relay Anal Output V DC mA Anal Output Start Point 20 0 Function Relay R2 NO NC NC NO Option Manual Calibratio...

Страница 13: ...B AT Specifications subject to change without notice USA 151203 Page 13 of 14 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 888 GO INTEC relevantsolutions com inteccontrols AT 3300_V3 Use...

Страница 14: ...ance It is recommended to check the PolyGard transmitter regularly Due to regular maintenance any performance deviations may easily be corrected Re calibration and part replacement in the field may be...

Отзывы: