![background image](http://html1.mh-extra.com/html/intec-controls/iva-420i/iva-420i_user-manual_2070537016.webp)
22
511399
2/07
Changing the
IVA-420I
Configuration
DIP Switch Settings
Changing the
IVA-420I
Configuration
DIP Switch Settings
Note: * When DIP Switch four (4) is set to 1, it is in statistic mode
(except for adjustment settings)
1
2
3
4*
5
6
7
8
Mode
VULBUS (2
01C)
0
0
0
0/1
0
0
0
0
Interrogation mode; Adr. 9-16
1
0
0
0/1
0
0
0
0
Interrogation mode; Adr. 1-8
0
1
0
0/1
0
0
0
0
Listen mode; Adr 9-16
1
1
0
0/1
0
0
0
0
Listen mode; Adr. 1-8
0
0
1
0
0
0
0
0
Output adjustment; 4mA
1
0
1
0/1
0
0
0
0
Interrogation mode; split adr 1-4,
9-12
0
1
1
0
0
0
0
0
Output adjustment: 20mA
1
1
1
0/1
0
0
0
0
Listen mode; split adr. 1-4, 9-12
0
0
1
1
0
0
0
0
Interrogation mode; statistic 1-16
0
1
1
1
0
0
0
0
Listen mode; statistic 1-16
MODB
US (301
C)
0
0
0
0/1
1
0
0
0
Modbus listen; Adr. 1-8
0
0
0
0/1
0
1
0
0
Modbus listen; Adr. 9-16
0
0
0
0/1
1
1
0
0
Modbus listen; Adr. 17-24
0
0
0
0/1
0
0
1
0
Modbus listen; Adr. 25-32
0
0
0
0/1
1
0
1
0
Modbus listen; Adr. 33-40
0
0
0
0/1
0
1
1
0
Modbus listen; Adr. 41-48
0
0
0
0/1
1
1
1
0
Modbus listen; Adr. 49-56
0
0
0
0/1
0
0
0
1
Modbus listen; Adr. 57-64
0
0
0
0/1
1
0
0
1
Modbus listen; Adr. 65-72
0
0
0
0/1
0
1
0
1
Modbus listen; Adr. 73-80
0
0
0
0/1
1
1
0
1
Modbus listen; Adr. 81-88
0
0
0
0/1
0
0
1
1
Modbus listen; Adr. 89-96
0
0
0
0/1
1
0
1
1
Not Available
0
0
0
0/1
0
1
1
1
Not Available
0
0
0
0/1
1
1
1
1
Not Available
IVA-420I User Manual