KNX Gateway DMX-Web K.DMXGW.01

5

Technical data

External supply
Rated voltage

AC/DC 24 V SELV (± 10%)

Mains frequency

50 / 60 Hz

Power consumption

max. 2.0 VA

Ambient conditions
Ambient temperature

-5 ... +45 °C

Storage/transport temperature

-25 ... +70 °C

Protection class

III

Fitting width

72 mm / 4 module

Weight

approx. 175 g

Network communication
IP transmission rate

10 / 100 Mbit/s

IP connection mode

RJ45 socket

KNX
KNX medium

TP

Commissioning mode

S-mode

Rated voltage KNX

DC 21 ... 32 V SELV

Connection mode KNX

Standard KNX/EIB connection terminals

Current consumption KNX

max. 5 mA

DMX
Input interface

USITT DMX512-A

Output interface

USITT DMX512-A

Connection of power supply and DMX
Connection mode

Screw terminal

single stranded

0.5 ... 4 mm²

Finely stranded without conductor sleeve

0.34 ... 4 mm²

Finely stranded with conductor sleeve

0.14 ... 2.5 mm²

6

Warranty

We reserve the right to make technical and formal changes to the product in the interest of tech-
nical progress.

We provide a warranty as provided for by law.

Please send the unit postage-free with a description of the defect to our central customer ser-
vice office:

Insta GmbH
Service Center
Hohe Steinert 10
58509 Lüdenscheid
Germany

6 / 7

82575434

06.02.2020

Содержание KNX Gateway DMX-Web K.DMXGW.01

Страница 1: ...part of the product and must remain with the end customer 2 Device components Figure 1 1 DMX input DMX IN DINX IN 2 DMX output DMX Out DMX Out 3 DMX earth GND 4 IP connection 5 Status LEDs 6 Programming LED 7 KNX connection 8 Programming button 9 Connection for external supply 10 Reset button 3 Function System information This device is a product of the KNX system and complies with the KNX directi...

Страница 2: ... group addresses is performed using a table stored in the gateway Assignment of the KNX group addresses and configuration of the operating mode are performed using the Windows software DMX Gate4 or higher The current software as well as a detailed description of the commissioning can always be found in the Internet Status LED 5 Figure 2 Power Error Lit up green Normal operation Orange flashing Inv...

Страница 3: ...signal The terminal pairs are only used individually depending on the operating mode Do not wire DMX bus in a star configuration Only use power supply units that supply secure extra low voltage SELV for power supply Connecting the device operating mode DMX master Figure 3 In the operating mode DMX master the gateway functions as a DMX data generator The ter minals DMX Out and GND are used for conn...

Страница 4: ...to the DMX bus the DMX cable has to be continued over terminals DMX In and GND Figure 4 Do not use DMX Out terminals Connect DMX bus to the terminals DMX In and DMX In 2 and GND 3 Connect KNX bus to the KNX terminals 7 Connect external power supply to one of the two terminal pairs AC DC 24 V 11 Connecting the terminating resistor operating mode DMX slave only Figure 5 A DMX bus should be provided ...

Страница 5: ... de The IP interface serves to connect the PC to the gateway A crosslink network cable might have to be used for the direct connection Connect PC to the gateway via IP connection Switch on PC Switch on external power supply Wait until the status LED Power Error flashes orange Start DMX Gate4 software and follow the instructions on the screen Load physical address The physical address is loaded wit...

Страница 6: ...andard KNX EIB connection terminals Current consumption KNX max 5 mA DMX Input interface USITT DMX512 A Output interface USITT DMX512 A Connection of power supply and DMX Connection mode Screw terminal single stranded 0 5 4 mm Finely stranded without conductor sleeve 0 34 4 mm Finely stranded with conductor sleeve 0 14 2 5 mm 6 Warranty We reserve the right to make technical and formal changes to ...

Страница 7: ...KNX Gateway DMX Web K DMXGW 01 Insta GmbH Postfach 1830 D 58468 Lüdenscheid Telefon 49 0 2351 936 0 Telefax 49 0 2351 936 1780 www insta de info insta de 7 7 82575434 06 02 2020 ...

Отзывы: