Installing the Rails to the Rack

Installing the Server to the Rack

3

5

1

2

3

4

6

1

5

 

Inner Rail

Rear Bracket

Outer Rail

Middle Rail

Front Bracket

1

Middle Rail

Inner Rail

2

4

2

Rack-Mounted Server Installation Guide 

V1.0

The rails are intended for square hole racks (9.2*9.2 mm, 9.5*9.5 mm) and round hole 

racks (Ø7.1 mm).

Insert the pins as indicated by the arrow until the pins are fully engaged.

Align and attach the keyholes of the inner rail to the stando s on the side of the

server, and then slide the inner rail toward the rear of the server to the locked

position.

Repeat Step 2 and Step 3 for the other inner rail.

Align and slide the inner rails to the middle rails along with the server. Gently 

push the server all the way into the rack.

Tighten the four captive screws.

Repeat Step 1-4 for the other rail.

NOTE: 

The front end and the rear end of the rail, and the two rails MUST be 

               installed at the same height.

Fully extend the inner rail until it clicks into a locked position. Repeat the same 

step to extend the other inner rail.

Pull up the locking tab to remove the inner rail.

Align the pins on the rear bracket to the desired position of the back of the rack. Press 

the locking latch as indicated by the arrow.

Insert the pins as indicated by the arrow until the pins are fully engaged.

Slide the inner rail to its fully closed position. Align the pins on the front bracket to the 

desired position of the front of the rack. Press the locking latch as indicated by the 

arrow.