2.0  System Operation

The SSC3 is controlled by a positive DC voltage on INPUT terminal. The turn ON voltage is +8.0 Vdc (Range of +8.0 

to 18.0 Volts).  The turn OFF voltage is <+4.0 Vdc. 

 Note that the input voltage must drop to under +4.0 volts, then 

increase to +8.0 volts to turn on again.

Certain fault conditions will cause the power switch to turn off and the LED to start blinking.  The SSC3 will remain 

latched off until the fault(s) are cleared, the INPUT voltage removed, then the INPUT voltage re-applied.  

The fault conditions that the SSC3 will recognize include:

1.  Over-current condition for greater than 1 Second.

2.  Loss of ground

3.  Under-voltage

4.  Over-voltage

5.  Over-temperature

6.  Shorted Load Detection

3.0  

Specifications

Current Rating:

 

200 Amps (SSC3-200A/B),    300Amps (SSC3-300)

Standby Current:

 

3.8 milliamps

Over-current Protection Trip:

 

205 Amps (+/- 2 Amps) for 1 sec (SSC3-200A/B) 

 

305 Amps (+/- 2 Amps) for 1 sec (SSC3-300)

Operational

 

Temperature Range:

 -40

o

 to +185

o

 F (-40

o

 to +85

o

 C) 

Over-temperature Shutdown:

 

> 185

o

 F (> 85

o

 C)  

Operational Voltage Range:

 

+7.0 to +18.0 Volts  

Fault Reset:

 

Remove Voltage (<4.0V) and then reapply a voltage (>8.0V) if no faults exist.

LED Indicator:

 

Switch on = LED ON, Switch off = LED Off, Faults exist = LED Flash

INPUT Signal Voltage Range:

 

+8.0 to 18.0 Volts (True - ON), < 4.0 Volts (False - OFF)

Standby Current:

 <3.8mA

Environmental: 

Designed to IP67

Power Terminal Torque:

 

Brass Bolts and Copper Washers

 (supplied with SSC3) 

torqued to between 10 to  

 

15 ft-lb.

Input and Gnd Terminal Torque:

  

8/32 Screw Terminal with Brass Nuts torqued to  between 4 to 5 Inch Lbs.

4.0  Installation Procedure

Do not weld on the vehicle with the SSC3 installed and connected as damage to the product may result.  If electric 

welding is necessary, disconnect the control INPUT terminal, and the cables attached to the LOAD and BAT+ terminals.  

Damage due to electric welding while the unit is installed will void InPower’s warranty.

4.1  Introduction

This manual provides instructions for installing InPower SSC3 Solid State Contactors.  It is important that you follow these 

instructions carefully and contact InPower if you need assistance or more information.  
You can contact InPower at:

InPower LLC

8311 Green Meadows Drive

Lewis Center, Ohio 43035

740-548-0965

www.InPowerLLC.com

!

!

WARNING!

Содержание SSC3

Страница 1: ...ith starting up into resistive loads inductive loads capacitive loads incandescent loads and identifies dead short faults The status LED indicator is on when the SSC3 is ON off when OFF and flashes to indicate a fault shutdown Automatic fault shutdown occurs for over current loss of ground high low battery voltage and or over temperature In a fault condition the contactor is latched in the off sta...

Страница 2: ...rational Temperature Range 40 o to 185 o F 40 o to 85 o C Over temperature Shutdown 185 o F 85 o C Operational Voltage Range 7 0 to 18 0 Volts Fault Reset Remove Voltage 4 0V and then reapply a voltage 8 0V if no faults exist LED Indicator Switch on LED ON Switch off LED Off Faults exist LED Flash INPUT Signal Voltage Range 8 0 to 18 0 Volts True ON 4 0 Volts False OFF Standby Current 3 8mA Enviro...

Страница 3: ...mal ef ficiency the mounting surface should be a thick metal surface such as an aluminum plate 1 8 x 16 x 16 inches or larger To facilitate heat transfer please apply a thin layer of silicon thermal material user supplied to the metal plate on the bottom of the SSC3 Smooth this out with a flat edge to insure there are no gaps Secure the contactor to the flat metal surface using four screws and tig...

Страница 4: ...K LOAD Ohms 0 20 INPUT BAT LOAD 12V 200 AMP SOLID STATE CONTACTOR 4 125 0 375 LED GND 2 375 4 125 3 40 2 50 1 688 1 125 3 125 3 775 0 75 0 875 Double Crimp Lugs Customer Supplied 0 813 1 4375 3 775 3 40 www InPowerLLC com Lot Code InPOWER the systems people SSC3 200A 7 0 18Vdc INPUT 8 0 18Vdc 0 625 Patented www InPowerLLC com Patents Electronic Switch 0 20 INPUT BAT LOAD 5 125 0 375 GND 4 125 3 77...

Отзывы: