3 Wiring
3
3.1.3
Recommended Models and Specifications of the Main Circuit Cables
The figure below shows the connectors of the main circuit cables. These connectors accompany the com
-
plete drive (model to be complemented at the time of producing in batches).
Figure 3-4 Figure of the main circuit cable connectors
Table 3-2 Recommended main circuit cable and cable model for SV820N series servo drive
No.
Drive Model
Single-phase 220 V
Rated
Input
Current (A)
Recommended
Input Power Cable
Rated
Output
Current (A)
Recommended
Output Power Cable
Recommended
Grounding Cable
mm
2
AWG
mm
2
AWG
mm
2
AWG
1
SV820N1S2C2C
4.6
2 x 0.5
20
2.80
2 x 0.5
20
0.50
20
details.
The following table describes the main circuit cables:
Table 3-3 Recommended main circuit cables
Cable Type
Allowed Temperature (
℃
)
Model
Name
PVC
General PVC cable
-
IV
PVC cable rated 600 V
60
HIV
Special heat resistant PVC cable
75
The following table describes the relation between the 3-cable diameter and current. The actual value shall
not exceed the value in the table.
Table 3-4
3-cable specifications
AWG Specification
Nominal Sectional Area
(mm²)
Allowable Current in Different Ambient Temperatures (A)
30
℃
40
℃
50
℃
20
0.519
8
7
6
19
0.653
9
8
7
18
0.823
13
11
9
Содержание SV820N Series
Страница 127: ...126 6 Trial Running 6 6 5 6 PLC Program 1 Add an FB file that edits the function block in the application...
Страница 128: ...127 6 Trial Running 6 2 The definition part of FB 3 Five function blocks in FB...
Страница 141: ...140 6 Trial Running 6 In section0 call the function block then the axis can be moved by the bus...
Страница 143: ...142 6 Trial Running 6 3 Open Visual studio and create a New Twincat3 Project...
Страница 146: ...145 6 Trial Running 6 Click OK Click OK...
Страница 147: ...146 6 Trial Running 6 Click Yes Click OK...
Страница 149: ...148 6 Trial Running 6 C The default RPDO list is as follows...
Страница 150: ...149 6 Trial Running 6...
Страница 152: ...151 6 Trial Running 6 7 Activate the configuration and switch over to the running mode Click...
Страница 157: ...156 6 Trial Running 6 Add a motion control library making it easy to call the control function block...
Страница 158: ...157 6 Trial Running 6 Create a new POU...
Страница 159: ...158 6 Trial Running 6 Create a new FB add MC_power MC_jog MC_home MC_absolute MC_reset to FB...
Страница 160: ...159 6 Trial Running 6 Call axis_motion in main Call the program in PLCTASK...
Страница 161: ...160 6 Trial Running 6 Compile the program if there is no fault configuration can be activated and then log in to the PLC...
Страница 181: ...Revision History Date Revised Version Revised Details May 2017 A00 First release...