8
Item
Description
CHARGE
Charging/
discharging
indication
Green, flashing once every 2s: Charging
Green, steady on: Charging is completed.
Green, flashing once every 0.5s: The input power supply fails.
The UPS provides the power supply (3s/4 A).
ERR
UPS fault
Red, steady on: The UPS is faulty due to output short circuit,
overload, or input overvoltage.
Safety
Insulation
voltage
withstanding
Input-output 3000 VAC (excluding the discharge tube and Y capacitor, 20
mA, 1 min)
Input-
enclosure
2000 VAC (excluding the discharge tube and Y capacitor, 20
mA, 1min)
Output-
enclosure
500 VAC (20 mA, 1 min)
Insulation impedance
(input-output, input/output-
enclosure)
> 100 MΩ (500 VDC/25℃ /70% RH)
Standard compliance
CE
EMC
Conducted emission
EN 55022 Class A
Immunity
EN 61000-6-2,3,4
Environment
Working temperature
-10℃ to +55℃
Storage temperature
-40℃ to +70℃
Overtemperature protection Protection upon 90℃ and automatic restoration upon 75℃
Working humidity
5% to 95%
Pollution degree
2
Mechanical Parameters
Mounting mode
DIN guide rail mounting
D x W x H
121 x 55 x 136 (excluding the rail)
Weight
< 1000 g
2 Mounting
2.1 Mounting Dimensions