20
7.0 Calibration Operation Instructions
1. Connect the required accessories to the inoRAC.
2. Connect the inoRAC to an adequate power supply via the receptacle on the
side of the control enclosure.
3. Turn on the inoRAC by placing the ON/OFF switch on the side of the control
enclosure into the “ON” position.
4. Start the inoRAC by pressing the “Racking Unit Control” button on the Operator
Panel.
5. Ensure the inoRAC is not connected to a circuit breaker. Ensure the inoRAC
is free to operate all accessories.
6. Select the operation to be performed, “Calibrate” on the Operator Panel.
7. Acknowledge each of the three checklist questions by selecting the “NO”
buttons to the right of each item. After all three checklist items are
acknowledged, the “CALIBRATE” button will display.
8. Select the “CALIBRATE” button. “CALIBRATING” will be displayed for
approximately 45 seconds.
9. When “CAILBRATION COMPLETE” is displayed, the actuator of the connected
accessory’s position reference is calibrated and the accessory is ready for use.