ICT N+1 REDUNDANT SERIES

INSTRUCTION MANUAL

Incorrect  wiring,  such  as  reverse  battery  connection,  may  result  in 
serious  damage  to  both  the  N+1  system  and  equipment  connected  to 
the system.

Do not block any of the vents on the outside of the unit.

Servicing of the unit should be done by ICT.

Ensure that the two voltage selector switches are both set correctly and 
to  the  same  position.  If  the  switches  are  incorrectly  set  it  will  result  in 
module failure.

The  system  must  be  operated  from  an  outlet  with  a  proper  grounding 
connection.

If  replacing  modules,  disconnect  power  from  any  external  source 
including the AC cord and any connected batteries.

WARNING:  High  leakage  current,  use  only  cord  set  provided  with  this 
equipment.

ICT N+1 REDUNDANT SERIES

SETUP

 WARNINGS

The ICT N+1 Redundant Series is a high reliablity, expandable DC power system. The system is designed with active current sharing technology to 
distribute the load current among the modules, reducing stress on individual components and increasing reliability. Each module is equipped with a 
high power shottky output diode for true redundancy.

This  series  comes  standard  with  system  monitoring  functions  through  a  D-Sub  connector,  with  signals  such  as  module  ok,  over  temperature 
warning, analog DC output current, fan failure, and AC fail. Battery backup terminals are provided for float charging an external lead acid battery and 
providing battery revert capability.

These instructions should be read before using the product and it should be saved for future reference.  A more detailed manual is available on 
request from ICT.

For 120V operation, set both voltage selection switches to the 
120V  position.  For  220V  operation,  set  both  to  the  220V 
position.

After  the  system  has  been  mounted,  connect  the  load  to  the 
terminal block at the rear of the unit. If desired, connect a 12V 
or 24V lead acid battery (matching the N+1 system voltage) to 
the battery terminals for float charging.

A  disconnect  device  must  be  provided  for  both  the  DC  power 
output  circuit  and  the  battery  backup  circuit  if  used.    The 
backup battery (if used) should be provided with an overcurrent 
device  suitable  for  the  available  short  circuit  current  of  the 
batteries used.

Connect the AC power cord to the unit and then to the available 
outlet.  Alternate AC cord types are available.

Turn  the  power  switch  on  the  front  of  the  unit  to  the  on 
position.

4

4

4

4

4

4

4

4

4

4

4

4

Input

Voltage

Range

Configs.

Output

Voltage

Output

Current 

(Cont.)

Output

Current 

(Peak)

Current

Limiting

Line

Regulation

Load

Regulation

Output 

Ripple 

(Max)

Efficiency

(Typical)

# of

Modules

N

NM

N

 - Standard     

NM 

- with LCD Meter

105-130/

205-250 VAC

13.8 VDC

+/- 300 mV

34.0 Amps

70.0 Amps

80.0 Amps

2.20%

1.00%

40 mV RMS

79%

ICT22012-70

2

105-130/

205-250 VAC

13.8 VDC

+/- 300 mV

105.0 Amps

105.0 Amps

120.0 Amps

2.20%

1.00%

40 mV RMS

79%

ICT22012-100

3

105-130/

205-250 VAC

13.8 VDC

+/- 300 mV

83.0 Amps

(90A @ 240 VAC)

127.0 Amps

160.0 Amps

2.20%

1.00%

40 mV RMS

77%

(80% @ 240 VAC)

4

105-130/

205-250 VAC

27.6 VDC

+/- 600 mV

17.0 Amps

36.0 Amps

40.0 Amps

2.20%

1.00%

40 mV RMS

83%

ICT22024-35

2

105-130/

205-250 VAC

27.6 VDC

+/- 600 mV

34.0 Amps

54.0 Amps

60.0 Amps

2.20%

1.00%

40 mV RMS

83%

ICT22024-50

3

105-130/

205-250 VAC

27.6 VDC

+/- 600 mV

41.0 Amps

(51A @ 240 VAC)

56.0 Amps

4

80.0 Amps

2.20%

1.00%

40 mV RMS

83%

(84% @ 240 VAC)

ICT22024-70

105-130/

205-250 VAC

13.8 VDC

34.0 Amps

35.0 Amps

--

36.0 Amps

2.20%

1.00%

35 mV RMS

80%

ICT12-30

105-130/

205-250 VAC

27.6 VDC

17.0 Amps

18.0 Amps

--

19.0 Amps

Redundant

Current

34.0 Amps

34.0 Amps

34.0 Amps

17.0 Amps

17.0 Amps

17.0 Amps

--

--

2.20%

1.00%

40 mV RMS

80%

ICT24-17

Modules

All complete systems are CSA C22.2 No 107.1, UL 1012 Approved

& FCC class A Compliant

SPECIFICATIONS

ICT22012-140