P32NDX – P32ND
OWNER’S MANUAL
11
Motor phase failure
output
•
Downstream contractor open
•
Motor not connected
•
Instability in the motor current
•
Drive controller oversized for motor
to the motor
•
Test the drive controller on a low power motor
or without a motor: set OPL to nO
O S F
Over voltage during
steady state
operation or during
acceleration
•
Line voltage too high
•
Line supply transients
•
Check the line voltage. Compare with the drive
controller nameplate rating
•
Reset the drive controller
P H F
Input phase failure
•
Input phase loss, blown fuse
•
Three-phase drive controller used on
a single-phase line supply
•
Input phase imbalance
•
Transient phase fault
NOTE: This protection only operates
with the drive controller running under
load
•
Check the connections and the fuses
•
Verify that the input power is correct
•
Supply three-phase power if needed
C F F
Configuration Fault
•
The parameter configurations are not
suited to the application
•
Restore the factory settings or load the backup
configuration, if it is valid
U S F
Under Voltage
•
Line supply too low
•
Transient voltage dip
•
Damaged precharge resistor
•
Check the line voltage
•
Replace the drive controller