17
6. Installation details
6.1 Wrench torque sheet for installation
Outside diameter
Torque
Additional
tightening torque
mm
inch
N.cm
N.cm
6.35
1/4
1500
(153kgf.cm)
1600
(163kgf.cm)
9.52
3/8
2500
(255kgf.cm)
2600
(265kgf.cm)
12.7
1/2
3500
(357kgf.cm)
3600
(367kgf.cm)
6.2 Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Rated current of appliance
Nominal cross-sectional area (mm²)
>3 and 6
0.75
>6 and 10
1.0
>10 and 16
1.5
>16 and 25
2.5
The cable size and the current of the fuse or switch are determined by the maximum current indicated
on the nameplate which located on the side panel of the unit. Please refer to the nameplate before