© MASS ELECTRONICS Pty Ltd 2014
Page 4
DS 1.29 - SENW5x - Wall Mounted Temperature Detector
December 2015
Parameter 1: Set Temperature Display Units
This parameter determines whether the temperature is
displayed in °C or °F.
•
Sets output in °F
•
Sets output in °C
[°C Default]
•
Sets the display and outputs to read in °F
[°F Default]
•
Sets the display and outputs to read in °C
• Selecting
will display the F or C beside the temperature.
• The setting used in P1 determines the units used globally (°F or °C).
Parameter 2: Temperature Setpoint Type
This parameter sets the setpoint display to either absolute (xx to yy°)
or Relative (±x°) on the display.
•
Absolute value (xx° - yy°)
[Factory Default]
•
Relative value (±xx)
• eg. ABS = 72.5°F
REL = -2.2°F
The setting used in P2 determines the SP Type used in P3 & P4.
Parameter 3: Temperature Setpoint Minimum Value
This parameter sets the minimum value for the setpoint.
Eng
Units
SP
Type
Function
Adjust value from 55.0 to 69.0°F, (increments of
0.5°F), Default = 65°F
[°F Default]
Adjust value from 12.0 to 20.0°C, (increments of
0.1°C), Default = 18°C
[°C Default]
or
Adjust value from -5° to 0°, (increments of
0.5°F/0.1°C), Default = -3°
• This setting is dependent on the values selected in P1 and P2.
• If altering P3, you must alter the setpoint range minimum in your
software programming.
Parameter 4: Temperature Setpoint Maximum Value
This parameter sets the maximum value for the setpoint.
Eng
Units
SP
Type
Function
Adjust value from 69.0 to 95.0°F (increments of
0.5°F), Default = 85°F
[°F Default]
Adjust value from 20.0 to 35.0°C (increments of
0.1°C), Default = 29°C
[°C Default]
or
Adjust value from 0° to +5°, (increments of
0.5°F/0.1°C), Default = +3°
• The setting is dependent on the values selected in P1 and P2.
• If altering P4, you must alter the setpoint range maximum in your
software programming.
Parameter 5: Temperature Setpoint Lockout
This parameter enables or disables the adjustment of the setpoint.
•
This setting locks the setpoint at the current value and
disables the Up/Down buttons
•
This setting enables the setpoint to be changed by the
user using the Up/Down buttons
[Factory Default]
Parameter 6: Occupancy Lockout
This parameter enables or disables the override button function.
•
This setting disables the Override button
•
This setting enables the Override button so the user
can request occupancy override
[Factory Default]
Parameter 7: Set Primary Display Mode
This parameter determines what is shown on the primary display.
•
The primary display is not used
•
Temperature value only
[Factory Default]
•
Temperature and setpoint values alternate every 5
seconds
•
Room temperature setpoint value only
Parameter 8: Set Secondary Display Mode
This parameter determines what is shown on the secondary display.
•
The secondary display is not used
•
Room temperature setpoint value only
[Factory Default]
Parameter 9: Display Resolution
This parameter sets the resolution for the digital display.
•
Sets a 0.1 resolution (xx.1)
[Factory Default]
•
Sets a 0.5 resolution (xx.5)
•
Sets whole number resolution (1)
Parameter 10: Backlight Duration
This parameter selects the backlight duration.
• 1-10 Adjust the setting using the Up or Down buttons
[Factory Default = 5 seconds]
Parameter 11: Temperature Sensor Calibration
This parameter adjusts the temperature display value ±10°.
• -10 to +10
Adjust value ±10° in 0.1° increments
[Factory Default is 0°]
Calibration of the display and the sensor input (at the controller) is
required.
Parameter 12: Sensor Firmware Version
This parameter displays the current firmware in the SENW58.
• 1.0
Example of firmware version
Parameter 13: Reset to Factory Defaults
The SENW58 may be reset to factory defaults.
1. Select P13,
will be displayed.
2. Press the
Up
button,
will be displayed.
3. Press the
Select
button,
will be displayed and the
sensor program will revert to the factory default values. Normal
operation will begin after the reset is complete.
The SENW58 sensor is factory calibrated.