DS 1.29 - SENW5x - Wall Mounted Temperature Detector

December 2015

Parameter 1: Set Temperature Display Units

This parameter determines whether the temperature is  

displayed in °C or °F. 

•   

  Sets output in °F 

•   

  Sets output in °C 

[°C Default]

• 

   Sets the display and outputs to read in °F 

[°F Default]

• 

   Sets the display and outputs to read in °C

• Selecting 

 will display the F or C beside the temperature.

• The setting used in P1 determines the units used globally (°F or °C).

Parameter 2: Temperature Setpoint Type

This parameter sets the setpoint display to either absolute (xx to yy°) 

or Relative (±x°) on the display.

• 

  Absolute value (xx° - yy°) 

[Factory Default]

• 

  Relative value (±xx) 

•  eg.   ABS = 72.5°F 

 

REL = -2.2°F

The setting used in P2 determines the SP Type used in P3 & P4.

Parameter 3: Temperature Setpoint Minimum Value

This parameter sets the minimum value for the setpoint.

Eng 

Units

SP 

Type

Function

Adjust value from 55.0 to 69.0°F, (increments of 

0.5°F), Default = 65°F 

[°F Default]

Adjust value from 12.0 to 20.0°C, (increments of 

0.1°C), Default = 18°C 

[°C Default]

or

 

Adjust value from -5° to 0°, (increments of 

0.5°F/0.1°C), Default = -3°

• This setting is dependent on the values selected in P1 and P2.
• If altering P3, you must alter the setpoint range minimum in your 

software programming.

 

Parameter 4: Temperature Setpoint Maximum Value

This parameter sets the maximum value for the setpoint.

Eng 

Units

SP 

Type

Function

Adjust value from 69.0 to 95.0°F (increments of 

0.5°F), Default = 85°F 

[°F Default]

Adjust value from 20.0 to 35.0°C (increments of 

0.1°C), Default = 29°C 

[°C Default]

or 

Adjust value from 0° to +5°, (increments of 

0.5°F/0.1°C), Default = +3°

• The setting is dependent on the values selected in P1 and P2.
• If altering P4, you must alter the setpoint range maximum in your 

software programming.

Parameter 5: Temperature Setpoint Lockout

This parameter enables or disables the adjustment of the setpoint.

• 

   This setting locks the setpoint at the current value and  

 

    disables the Up/Down buttons

• 

    This setting enables the setpoint to be changed by the  

 

     user using the Up/Down buttons 

[Factory Default]

Parameter 6: Occupancy Lockout

This parameter enables or disables the override button function.

• 

  This setting disables the Override button

• 

   This setting enables the Override button so the user   

 

    can request occupancy override 

[Factory Default]

Parameter 7: Set Primary Display Mode

This parameter determines what is shown on the primary display. 

• 

   The primary display is not used

• 

   Temperature value only 

[Factory Default]

• 

   Temperature and setpoint values alternate every 5    

 

    seconds

• 

   Room temperature setpoint value only

Parameter 8: Set Secondary Display Mode

This parameter determines what is shown on the secondary display.

• 

   The secondary display is not used

• 

   Room temperature setpoint value only 

[Factory Default]

Parameter 9: Display Resolution

This parameter sets the resolution for the digital display. 

• 

  Sets a 0.1 resolution (xx.1) 

[Factory Default]

• 

  Sets a 0.5 resolution (xx.5) 

•   

Sets whole number resolution (1) 

 

Parameter 10: Backlight Duration

This parameter selects the backlight duration.  

•  1-10  Adjust the setting using the Up or Down buttons  

 

 

[Factory Default = 5 seconds]

Parameter 11: Temperature Sensor Calibration

This parameter adjusts the temperature display value ±10°.  

•  -10 to +10 

Adjust value ±10° in 0.1° increments 

  

[Factory Default is 0°]

Calibration of the display and the sensor input (at the controller) is 
required.

Parameter 12: Sensor Firmware Version

This parameter displays the current firmware in the SENW58. 

•  1.0 

Example of firmware version

Parameter 13: Reset to Factory Defaults

The SENW58 may be reset to factory defaults. 

1. Select P13,  

  will be displayed.

2. Press the 

Up

 button, 

 will be displayed.

3. Press the 

Select 

button, 

 will be displayed and the 

sensor program will revert to the factory default values. Normal 

operation will begin after the reset is complete.

The SENW58 sensor is factory calibrated.

Содержание SENW51

Страница 1: ...nclosure design Wall mounted Displays Temperature and Setpoint at a glance Onboard temperature sensor Displays Fahrenheit F or Celsius C Push button interface for a Temperature setpoint adjustment b Occupancy override Display available on SENW58 model only Temperature setpoint adjustment and override available on SENW58 model only Installation Wiring The SENW5x detector should be installed in an e...

Страница 2: ...ATURE SENSOR Resistance NTC 10 000Ω thermistor 10K 2 Accuracy 0 36 F 0 2 C from 32 to 158 F 0 to 70 C Inputs and Outputs AVAILABLE OUTPUTS Temperature Temperature Temp Resistance 10K 2 thermistor Isolated Setpoint STPT 0 to 10VDC configurable setpoint signal ref to power GND OCCUPIED INPUT Occupancy OVR Occupied 10VDC Man displayed Unoccupied 0VDC Man not displayed ref to power GND Controls and Di...

Страница 3: ...Temp and Setpoint P7 Secondary Display Indicates Temperature Setpoint P8 The display can be adjusted for resolutions of 0 1 0 5 or 1 The backlit display has two modes Active and Inactive Active When a button press is detected the display will illuminate Inactive When no button activity is detected for 5 seconds the display will become dull The is displayed on the SENW58 to indicate Occupied or Uno...

Страница 4: ... or disables the adjustment of the setpoint This setting locks the setpoint at the current value and disables the Up Down buttons This setting enables the setpoint to be changed by the user using the Up Down buttons Factory Default Parameter 6 Occupancy Lockout This parameter enables or disables the override button function This setting disables the Override button This setting enables the Overrid...

Страница 5: ...ates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense Modifications to this device may void the autho...

Страница 6: ...61 7 3421 9100 Fax 61 7 3421 9101 Email sales innotech com au www innotech com au The INNOTECH device and the word INNOTECH are registered or unregistered trademarks of Mass Electronics Pty Ltd in Australia USA and other countries Configurations are available from the Innotech Website by clicking here Please note that the Fault Limits should be set as shown Please note that the Fault Value should ...

Отзывы: