© MASS ELECTRONICS Pty Ltd 2011
Models
:
ISS01 – innTOUCH Smart Sensor
ISS02 – innTOUCH Smart Sensor with Real Time Clock (RTC)
ISS03 – innTOUCH Smart Sensor with Universal Inputs (UI)
ISS04 – innTOUCH Smart Sensor with RTC and UI
Overview
The Innotech innTOUCH Smart Sensor is a wall mounted remote
Human Machine Interface (HMI) panel that provides a user interface
for supported Innotech MiniMAX, VAVMax, MicroMAX, Omni C20x and
Omni C40x controllers.
The innTOUCH Smart Sensor has a single communications channel,
with data transfer occurring through the power supply interface.
Power and communication are provided through the 2-way
Combicon connector.
One innTOUCH Smart Sensor can interface with a supported
controller. All data points on the innTOUCH Smart Sensor are
updated at the same rate as the controllers.
DS 13.05
October 2018
innTOUCH Smart Sensor
Applications
The innTOUCH Smart Sensor extends the capabilities of the
supported controllers. innTOUCH provides an easy to read visual
display of control values, and allows modifications to certain
parameters using the intuitive LCD and push button interface.
•
Provides a HMI for the controller to which it is connected
•
Immediate access for programming parameters
Features
•
Icon based backlit Liquid Crystal Display (LCD)
•
Modern, attractive enclosure design
•
Four universal inputs (optional)
•
One integrated thermistor input
•
Real Time Clock (optional)
•
Push button interface
•
Direct interface with the MM01C, MM02C, VM01C, UM01C, OMC20,
OMC20D, OMC40 and OMC40D controllers
•
Two wire single twisted pair, shielded or unshielded connection
from controller provides both comms and power
•
Wall mounted device
Model designations
Thermistor Input
Universal Inputs
Real Time Clock
ISS01
—
—
ISS02
—
ISS03
—
ISS04
Installation / Wiring
The innTOUCH Smart Sensor should be installed in an environment
that does not exceed the maximum operating parameters of the
device. It should be mounted in a clean and dry environment free of
vibration, and properly ventilated.
The cable providing both power and communication must be 2 core
shielded twisted pair cable. Polarity (+/–) MUST be observed when
connecting power.
The recommended cable length is maximum 30 metres. The cable
should not be run in parallel with conductors carrying high current.