DS 15.09 - GENII CSAH REM - Control Station After Hours Module

August 2013

Program Functions On The GENII CSAH REM

Start Programming Mode

To enter Programming Mode depress and hold the 

 and 

ON

OFF

 buttons for 5 seconds. The display will become blank 

indicating that you are in the Programming Mode. Release both 

keys and the display will show parameter 0. 

Whilst in the programming mode the following buttons are 

active:

ON

OFF

 

Change to the next parameter.

 

Increase the current parameters value.

 

Decrease the current parameters value.

Parameter 0: Rem Address

The display will show current REM Address of the device.

•  The range of address is 0 to 15

•  The default address is 0

Parameter 1: Maximum Input Value

The display will show the Maximum Input Value to which the 

module’s input can be set.

•  The range of Maximum Input Value is 0.0 to 99.9

•  The factory default setting is 30.0

Parameter 2: Minimum Input Value

The display will show the Minimum Input Value to which the 

module’s input can be set.

•  The range of Minimum Input Value is 0.0 to 99.9

•  The factory default setting is 15

Exit Programming Mode

To exit the Programming Mode depress the 

ON

OFF

 and 

       

buttons and the new setting will be saved.

Start Up Default Settings

The GENII CSAH REM Module can be set to start with a default 

setpoint. 

1. To set the start up default setpoint, adjust the GENII CSAH 

REM Module to the desired setpoint and then press and 

hold the 

ON

OFF

  and 

 buttons for 5 seconds. 

2. The display will become blank indicating that the new 

setpoint has been saved.

Operating Functions On The GENII CSAH REM

Numerical Output

The GENII CSAH REM Module will display a 3 digit, single decimal place 

analogue output value during normal operation.

Numerical Input

The GENII CSAH REM Module will provide a 3 digit, single decimal 

place analogue input value to the GENESIS Controller during normal 

operation.

This value can be modified by pressing the 

 button to increment by 

0.1 or the 

 button to decrement by 0.1.

Momentary Digital Input Value

The 

ON

OFF

 button on the GENII CSAH REM Module provides a digital input 

value to the GENESIS Controller during normal operation. 

This operates as a standard momentary switch, i.e. Press the 

ON

OFF

 

button produces a momentary digital input to the GENESIS controller.

Digital Output Led

The GENII CSAH REM displays a digital state via the system LED during 

normal operation.