© MASS ELECTRONICS Pty Ltd 2006
Models:
GENII CSAH REM:
Control Station After Hours Module
DS 15.09
August 2013
GENII CSAH REM
Control Station After Hours Module
Applications
Expands GENESIS Controller capabilities by providing a numeric output
display, numerical value input, a single momentary digital input switch
and single LED display output for distributed control via RS485. The
GENII CSAH REM Module provides a visual display of a control value and
a means to set a parameter.
Application Notes
A GENESIS Controller must have version 4.0 firmware installed to
support REM Modules. Version 4.1 or higher Config Software must be
used to configure a GENESIS Controller that has a CSAH REM Module
connected to it.
One GENESIS Controller can have up to 9 GENII CSAH REM Modules*
connected to it via the REM comms bus. For detailed connection
information to the pre-version 5 GENESIS Digital Controller Family,
please refer to DS 99.03
Overview
The Innotech GENII CSAH REM Momentary Digital Input Control
Station Module is an expansion device for the GENESIS range of
Digital Controllers.
The module is powered by 24VAC and provides a limited User
Interface to the GENESIS Controller. There are no physical
connections between field equipment and the GENII CSAH REM,
all input/output values are edited and viewed on the wall unit.
The GENII CSAH REM may be located remotely from the GENESIS
Controller providing a distributed User Interface for the system.
The GENII CSAH REM is configured via the wallplate and
programmed via the GEN2Config Software.
The GENII CSAH REM communicates with the Genesis Controller
via the REM Comms port. The remote link uses RS-485 at a baud
rate of 38400. For pre-version 5 controllers, a Gen II RMI Remote
Module Interface is required. Please refer to DS 15.01 for further
information.
Features
• One single decimal place numerical value input
• One single decimal place numerical output
• One momentary digital input and one LED digital display
output
• Housed in a switchplate that mounts in standard electrical
wall plates
• RS485 interconnection between REM Modules
• 24VAC operation
• Wiring Diagrams for modules generated by GEN2Config
Software
• Adjustable user input range
• Configurable power on settings
Approvals
The GENII CSAH REM conforms to:
• EN 55011 Class B Group 1 & AS/NZS 2064:1997 for RCM
Labelling
• FCC Title 47 CFR, Part 15 Class A for FCC Marking
• UL listed to UL916, File Number E242628