background image

© MASS ELECTRONICS Pty Ltd  2006

Page 2

DS 15.08 - GENII CS REM - Control Station Module

August 2013

Specifications

Power Supply

•  Voltage: 24VAC ±10% @ 50/60Hz

•  Power Consumption: 3VA max

The operating voltage must meet the requirements of Safety Extra Low 
Voltage (SELV) to EN60730. The transformer used must be a Class 2 safety 
transformer that has the energy and voltage limiting characteristics as 
described in the National Electrical Code, ANSI/NFPA70. It must also be sized 
and fused in compliance with local safety regulations.

Inputs

•  Push buttons for adjusting control values

•  Push button for toggling of “digital function”

•  Push button for timer initiation

Outputs

•  No physical outputs

•  Display of Temperature and Setpoint

Terminal Identification

1  

24VAC Supply

2  

0VAC Supply

3 Earth

TERMINAL 3 is for the protection of the Comms circuitry and must 

be connected to a good electrical bonded Earth.

COMMS Connection

SHLD 1   Shield from incoming Comms Cable.

+  

RS 485 (+) signal.

-  

RS 485 (-) signal.

SHLD 2   Shield from outgoing Comms Cable.

Temperature Ratings

•  Storage  

0 to 50°C non-condensing

•  Operating  

0 to 40°C non-condensing

Enclosure

The GENII CS REM Modules are housed in switchplate that mounts in 

standard electrical wall plates.

Colour:    

White

Mounting:  

Wall mounted

Installation

•  The Cable run between the GENII CS REM and the GENII RMI 

should not exceed 500 metres. The Comms wiring requires cable 

especially suited for RS485. Other shielded cable is not suitable 

and will cause spasmodic Comms failures.

•  Strictly follow the guidelines when installing the Comms wiring as 

outlined in the Genesis II Installation Manual.

•  Mount the GENII CS REM in a dry and clean location free of excess 

vibration. 

The REM address must be set by programming Parameter 0. 

Please refer to the Program Functions section of this data sheet 

for more specific information regarding this.

Wiring

•  The cable used for RS485 Comms must be shielded single twisted 

pair, 120 ohms character impedence, 36 to 45pF per metre 

capacitance between conductors.

•  The Comms cable must be organised as a bus topology. That is, 

starting at one end, devices are connected to it until the other 

end of the cable is reached. No “stubs” are allowed. To connect a 

device to the cable, as cut is made in the cable at the point where 

the device is to be situated along it. Then, the two new ends of 

the cable are wired into the device. The shields from the two new 

ends are then terminated into the terminals marked SHLD1 and 

SHLD2. 

Refer to the Genesis Network Installation Instructions for more 

information.

FCC Class A Notice

This device complies with Part 15 of the FCC Rules. Operation is 

subject to the following two conditions:

•  This device may not cause harmful interference.

•  This device must accept any interference received, including 

interference that may cause undesired operation.

Note – This equipment has been tested and found to comply with the limits for a Class A 

digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide 

reasonable protection against harmful interference when the equipment is operated 

in a commercial environment. This equipment generates, uses and can radiate radio 

frequency energy and, if not installed and used in accordance with the instruction 

manual, may cause harmful interference to radio communications. Operation of this 

equipment in a residential area is likely to cause harmful interference in which case the 

user will be required to correct the interference at his own expense. Modifications to this 
device, may void the authority granted to the user by the FCC to operate this equipment.

Содержание GENII CS REM

Страница 1: ... to the GENESIS Controller There are no physical connections between field equipment and the GENII CS REM all input output values are edited and viewed on the wall unit The GENII CS REM may be located remotely from the GENESIS Digital Controller providing a distributed User Interface for the system The GENII CS REM is configured via the wallplate and programmed via the GEN2Config Software The GENI...

Страница 2: ...ss must be set by programming Parameter 0 Please refer to the Program Functions section of this data sheet for more specific information regarding this Wiring The cable used for RS485 Comms must be shielded single twisted pair 120 ohms character impedence 36 to 45pF per metre capacitance between conductors The Comms cable must be organised as a bus topology That is starting at one end devices are ...

Страница 3: ...ess and hold the ON OFF and buttons for 5 seconds 2 The display will become blank indicating that the new settings are saved Operating Functions On The GENII CS Rem Numerical Output The GENII CS REM Module will display a 3 digit single decimal place analogue output value during normal operation Numerical Input The GENII CS REM Module will provide a 3 digit single decimal place analogue input value...

Страница 4: ...UTOR Australian Owned Designed Manufactured by Mass Electronics Brisbane Phone 61 7 3421 9100 Fax 61 7 3421 9101 Email sales innotech com au www innotech com au The INNOTECH device and the word INNOTECH are registered or unregistered trademarks of Mass Electronics Pty Ltd in Australia USA and other countries ...

Отзывы: