background image

12

 

Up / AT  Key :

 

Used  in  Program  mode  to  increment  parameter 

 

value.

 

 auto-tuning.

 

Touch & hold this key for 2 seconds to start or stop

11

 

Exit Key :

 

Press this key to save the setting value and to exit   

the programing mode.

9

 

Press & hold this key atleast 8 seconds to enter 

 

in Level2.

 

Press & hold this key atleast 1 seconds to enter 

 

in set  point mode.

 

Press & hold this key atleast 4 seconds to enter 

 

in Level1.

 

Next key : 

 

Used to enters parameters level, moves to next 

 

parameters.

10

 

value.

 

Down / Reset Key : 

 

Used in Program mode to decrement parameter

 

Used to Reset SVC time.

Sr. 

No.

Description

Turns ON while control output is ON.

Turns ON when auto tunning is in progress.

4

5

Turns ON when keypad is locked.

3

6

Turns ON when service time elapsed.

O

Turns ON when the process value is > 5 C than set 
point.

O

Turns ON when the process value is within the 5 C 
range of the set point.

O

Turns ON when the process value is < 5 C than set 
point.

8

7

2

 

RUN mode : Displays current measured value.

Process Value

 

SETTING mode : Displays parameter.

1

Input types & Input range

Input Type

Thermocouple

J

K

1

Decimal

Point

1

Display

O

Input Range ( C)

O

-50 to 750 C

O

-50 to 999 C

RTD

Pt

100

1

0.1

O

-99 to 400 C

O

-9.9 to 99.9 C

Operating Manual

Introduction

Caution for your safety

Notice: 

The information in this document is

 

subject

 

 to change in 

order to improve reliability , design or function without prior notice 
and does not represent

 

a commitment on the part of the company. 

In no

 

event will the company be liable for direct, indirect, special, 

incidental  or  consequential  damage  arising  out  of  the  use  or 
inability to use the product or documentation, even if advised of 
the possibility of such damages. No part of this manual may be 
reproduced or transmitted in any form or by any means without 
the prior written permission of the company.

Probe :

To give a correct reading, the probe must be installed 

in  a  place  protected  from  thermal  influences,  which  may 
affect the temperature to be controlled. 

WIRING:

 The probe and its corresponding wires should

 

never be 

installed in a conduit next to control or power

 

supply lines. The 

electrical wiring should be done as shown in the diagram. The 
power supply circuit should be connected to a protection switch. 
The terminals admit wires of upto 2.5sq mm.

WARNING:

  Improper wiring may cause irreparable damage and 

personal  injury.  Kindly  ensure  that  wiring  is  done  by  qualified 
personnel only.

Controller:

Controller  should  be  installed  in  a  place 

protected  by  vibration,  water  and  corrosive  gasses  and 
where  ambient  temperature  does  not  exceed  the  values 
specified in the technical data.

Maintenance:

 Cleaning: Clean the surface of the controller with a 

soft moist cloth. Do not use abrasive detergents, petrol, alcohol or 
solvents.

Product Mounting

Installation :

 Fixing and dimensions of panel models:

To fix the unit, slide the fastener   1   through the guides   2   as per the 
position shown in the figure. Move the fastener in the direction of the 
arrow, pressing tab   3   it permits to move the fastener in the opposite 
direction of the arrow. 

45.5mm

45.5mm

Panel Cutout

Dimensions 

Connection Diagram

When power is supplied, whole display part will be flash for 
6 sec and then enters in to RUN mode.

1. Whole display Part

2. Second Screen 

Initial Display when Power is ON

Technical Specification

Display              : 

3 X 20mm 7 segment White display,

O

 

 

  1 C for Thermocouple (J, K) input

 

 

  85 to 265 VAC/DC on request.

Mounting         

Flush panel mounting with fasteners

Protection       

:

 IP65 Front

                               < 

2.5sq mm terminal only.

Data storage   

Non-volatile flash memory

Storage temp    : 

-25°C to 60°C (non-condensing)

Power input    

:

 230 Vac ±15 % , 50-60Hz Standard. 

Control output   : Relay : 

10A, 230V AC or 

Connections   

Terminal connectors. 

 

 

  SSR (field selectable) : 10V DC, 30mA

 

 

  Thermocouple : J, K 

Input Type    

:

 RTD : Pt100

O

O

Resolution 

 

0.1 C / 1 C for RTD (Pt100) input

Dimensions    

Frontal : 48 X  48mm,  Depth : 78mm

O

Display Accuracy:

 RTD : 0.1% of F.S +/- 1 C

Housing          

Polycarbonate Plastic

Panel Cutout  

45.5 X 45.5mm

 

 

  7 Iconic LEDs for Indication

Operating temp.  : 

0°C to 60°C (non-condensing)

Operating humidity : 

20% to 85% (non-condensing)

 

 

  Thermocouple :  0.3% of F.S

Sampling Period : 

1 second

                               (20 min of settling time for TC)

Parameter Setting Mode

Function: Sets the upper limit of PV input.

5

Parameter

Function: Sets the lower limit of PV input.

4

Parameter

For J type sensor

For J type sensor

Display will show        . User can change         value using UP/ 
DOWN keys. Holding the key, will change the value at a faster 
rate. Press        key to store the desired value & move on to 
the next parameter. Set value also can be stored by pressing        
Key

Function: To set control set point.

1

Parameter

Press & hold        key for 1 seconds.

SP Setting

6

Parameter

Function : To set service time.

Example: 

If user set Service time to 10 days, then after 10 

days  of  continuous  service  of  machine,  the  SVC  icon  on 
controller will lit to indicate that service time has been elapsed 
or its time to service the machine

Service Time notify the machine user to carry out the machine 
maintenance setted at predefined time or to indicate that, the 
machine has worked for certain days.

Min

Max

Fac.

999

Day

Function: Sets input correction.

3

Parameter

Min

Max

Fac.

In time it may be possible that the display may be offset by a 
degree or so.
To compensate for this error, user may need to add or minus the 
degrees required to achieve the correct temperature.

O

Example : 

The temperature on the display is 28 C, whereas the 

O

actual  temperature  is  30 C.  User  will  have  to  set  the  "        " 

O

parameter  to  2 C,  which  means  that  once  out  of  the 

O

programming mode, the temperature on display will be   30 C 

O

O

(28 C+ 2 C).

O

-20 C

O

20 C

O

0 C

LEVEL1 Parameter

Function: Sets the type of input sensor .

2

Parameter

Min

Max

Fac.

For J type sensor

For type of input sensor & range please refer 

"Input types & 

Input range"

 table.

8

9

10

11

12

Sets cycle time for PID action.

Sets proportional band.

Sets integration time.

Sets differential time.

Sets the 

hysterisis.

Runs auto tuning.

Set control action for relay / SSR.

Index

Sr. 

No.

Para.

Description

1

3

4

5

6

7

Control set point.

Sets the type of input sensor .

Sets input correction.

Sets the lower limit of PV input.

Sets the upper limit of PV input.

13

14

15

16

Factory reset parameter.

Level1 Parameter

Sets Control output.

Lock keypad.

2

LED Indications

User Interface

Technical Specification

Initial display when Power is ON

Parameter setting mode

Working

Level2 Parameter

Error Messages 

Input types & Input range

Set service time.

Min

Max

Fac.

O

0 C

7

Parameter

Function : To restore default settings of 
the controller.

When Set to Yes all parameter are programmed to factory 
values.
Useful to debug setting related problems.

Min

Max

Fac.

Min

Max

Fac.

O

-50 C

Once set at a particular value, this will not allow the set point 
to go above this value.

When changing the setting value and SV > HSV, SV is reset 
as HSV.

Sets the maximum limit for set point adjustment. It can be 
set from LSV+1 value to maximum specified range of 
selected sensor.

While changing the sensor type       ,       ,       ,            
parameters of level1 will reset accordingly.

Once set at a particular value, this will not allow the set point 
to go below  this value.

When changing the setting value and SV < LSV, SV is reset 
as LSV.

Sets the minimum limit for set point adjustment. It can be set 
from minimum specified range of selected sensor to HSV-1 
value.

Function: Sets cycle time for PID action.

10

Parameter

LEVEL2 Parameter

Function: Runs auto tunning.

9

Parameter

This parameter will  be prompted only if selected control 
action is PID in control parameters. 

This parameter used to set YES/NO to start and stop  Auto-
tuning.
When Setting as      , the unit starts  auto-tuning. After 
Completing          is automatically Set.
During auto-tuning, the AUTO indicator continuously ON.

Function: Sets control action for 
relay/SSR.

8

Parameter

This  parameter  used  to  set  required  control  action  for 
relay/SSR.

Min

Max

Fac.

= PID

= No action

= Reverse

= Forward

Min

Max

Fac.

Cycle time also known as duty cycle, the total length of time for 
the controller to complete one ON/OFF cycle. 

Example  :

  With  a  20  second  cycle  time,  an  on  time  of  10 

seconds  and  an  OFF  time  of  10  seconds  represents  a  50 
percent power output. The controller will cycle ON and OFF 
while within the proportional band.

Min

Max

Fac.

1 sec 60 sec 3 sec

Function: Sets differential time.

13

Parameter

Sets the differential time of PID parameter.

Min

Max

Fac.

0

sec

999

sec

30

sec

Setting "0" will turn OFF differential.

Term D is a best estimate of the future trend of the SV-PV error, 
based  on  its  current  rate  of  change.  It  is  sometimes  called 
"anticipatory control", as it is effectively seeking to reduce the 
effect  of  the  SV-PV  error  by  exerting  a  control  influence 
generated  by  the  rate  of  error  change.  The  more  rapid  the 
change, the greater the controlling or dampening effect.

Function: Sets proportional band.

11

Parameter

Sets the proportional band of PID parameter.

Min

Max

Fac.

O

0.1 C

O

99.9 C

O

10.0 C

Function: Sets integration time.

12

Parameter

Sets the integration time of PID parameter.

Min

Max

Fac.

0

sec

999

sec

120

sec

Example :

 If the (SV-PV) error is large and positive, the 

control output will be proportionately large and positive and 
vice versa if error is negative.

Term P is proportional to the current value of the SV-PV 
error . 

Term I accounts for past values of the SV-PV error and 
integrates them over time to produce the I term. 

Example  :

  If  there  is  a  residual  SV-PV  error  after  the 

application of proportional control, the integral term seeks to 
eliminate the residual error by adding a control effect due to the 
historic cumulative value of the error. 

Setting "0" will turn OFF integration.

A proportional–integral–derivative controller (PID controller or three 

term controller) is a control loop feedback mechanism widely used in 

industrial control systems and a variety of other applications requiring 

continuously  modulated  control.  A  PID  controller  continuously 

calculates  an  error  value  as  the  difference  between  a  desired 

setpoint (SV) and a measured process variable (PV) and applies a 

correction  based  on  proportional,  integral,  and  derivative  terms 

(denoted P, I, and D respectively) which give the controller its name.

-1

O

-50 C

Min

Max

Fac.

O

750 C

O

750 C

    
+1

User can Upload parameters settings from one controller 
and download them to multiple controllers.

This will make on site parameter setting easy.

Pro-key (On Request)

The Auto-tuning function automatically computes and sets the 
proportional band (P), Integral time (I), Derivative time (D) as 
per process characteristics.

After Auto-tuning is complete the 

"AUTO"

 led will turn OFF.

While Auto-tune is in progress 

"AUTO"

 led will turn ON.

Carry out the auto-tuning again, if there is a change in setpoint 
or process parameters. 

If auto -tuning is not complete after 3-4 cycles, it is suspected to 
fail. In this case, check the wiring & parameters such as the 
control action, input type etc.

PID-time proportional
with auto reset & rate 

Working

2. ON/OFF control action (For reverse  mode)

The  relay  is  ‘ON’  up  to  the  set  temperature  and  cuts”OFF” 
above the set temperature . As the temperature of the system 
drops  ,the  relay  is  switched  ‘ON’  at  a  temperature  slightly   
lower than the set point .

The  difference  between  the  temperature  at  which  relay 
switches ‘OFF’ is the hysteresis or dead band.

HYSTERESIS:

1. Auto tuning

Note : In Auto Tunning  running time, user can not change 
the parameter value.

48mm

1

2

3

CONTROLLER

GASKET

PANEL

Side Lock

Press  &  hold          key  for  4  seconds  to  enter  into  Level1 
parameter setting(       will flash).     

Press the         key to save the set value and to come out of 
parameter setting after changing the set value. 

When release the key,       will flash.
Press 

UP/DOWN

 keys to modify the set value and to go to the 

next parameter by pressing        key.

Press 

UP/DOWN

 keys to modify the set value and to go to the 

next parameter by pressing        key.

        will flash.

Press  &  hold          key  for  8  seconds  to  enter  into  Level2 
parameter setting(        will flash). When release the key, 

Press the         key to save the set value and to come out of 
parameter setting after changing the set value. 

TCW-S1-UR2-230AC

TM

48mm

48mm

TCW

User Interface

TCW

2

1

3

5

4

6

7

8

11

9

10

12

L

N

RTD

TC

+

-

NO

C

NC

SSR

+

-

Отзывы: