Integriti Prisma-SIFER Terminal Installation Manual.
6
Access Control
At present, the Prisma-SIFER Terminal can be used for Door Access Control in “PIN
Only”, “PIN or Card” or “Card & PIN” modes to provide the Card &/or PIN code entry.
However, the following conditions currently apply:
1)
The Graphic Terminal does not currently support any Inputs or Outputs. Therefore,
the Door must also be associated with a Reader Module, and all Inputs and Outputs
associated with the Door must be connected to that Reader Module.
2)
The Lock Auxiliary for the Door must be the Reader Module Lock Auxiliary, not the
Terminal Lock Auxiliary.
Commissioning
When installation is complete, power up the Terminal.
The startup screen will display “Waiting for LAN Connection” along with the Module
number, Firmware Version, and a <Config> Function key. This screen is displayed for:
- 30 seconds or until <Config> or <END> is pressed if Tamper switch is unsealed.
- 2.5 seconds if the Tamper Switch is sealed.
•
To view and/or change the Module Number (Set to 01 at the factory) or the Colour
Scheme, press the <Config> Function key while this initial screen is displayed, then
go to “Colour Scheme and Terminal Number” below.
•
To exit the startup screen and go to the normal default display, press the <END> key.
If the “Waiting for LAN Connection” message is shown for more than 30 seconds, the
Module has not enrolled on the LAN. This could be due to:
- A LAN cabling and/or connection problem.
- Another Graphic Terminal with the same Module Number is already enrolled.
- The number of Modules on the LAN exceeds the limits of the Memory Configuration or
the licensing for this Control Module.
When the startup screen closes, the display may show a Terminal message, Time/Date,
Area status, or Alarm message, etc. This means the Module Number has been accepted.
To change the Module number or Colour scheme you will need to enter the Configuration
mode as described above.
To change other Graphic Terminal parameters, you will need to enter Setup mode as
described in “Graphic Terminal Setup” on the following page.
Colour Scheme and Terminal Number.
a) Enter Configuration mode as described above.
b) To change the colour scheme, press the <Colour> Function key.
b) To change the Module Number, choose a number that isn’t already used by another