EDAM-4200 Series User’s manual Version 1.03
8.4.55
~AA4V
Read Power-on or Safe DO value of module
Description: Read power-on or safe DO value of module
Command:
~AA4V [CHK](cr)
Syntax:
~
Command leading code
AA
Module address ID(01 to FF , Always 01)
4
command for read the power-on DO value or the safe DO value of a module
V
Read power-on value or safe value
= P - read power-on value,
= S - read safe value.
CHK
Check sum
(cr)
Carriage return
Response:
!AADDDD (cr)
Valid command.
?AA[CHK](cr)
Invalid command
!
Delimiter for valid command
?
Delimiter for invalid command
AA
Module address ID
DDDD
powe-on or safe value.(0000~FFFF)
CHK
Check sum
(cr)
Carriage return
Example 1:
Read Power on value and return power-on value 5A5A.
command:
~014P(cr)
response:
!045A5A(cr)
Example 2:
Read Power on value and return safe value AA00.
command:
~014S(cr)
response:
!04AA00(cr)
Ref. command:
~**, ~AA1, ~AA0, ~AA4V, ~AA5V, ~AA2, ~AA3PPP , ~AA3P, ~AA3EVVV
Printed Date: 27 February 2018
142