5.1 Temperature Control Range Setting (HS, HD, DD)
When controller works normally, LED displays current measured value of humidity, then
starting the recognition and translation of humidifying and dehumidifying automatically.
When the measured humidity
Differential Value)
, entering into the status of dehumidification, indicator lamp of
dehumidification will on, relay of dehumidification will work.
indicator light is flickering
protection. When the measured temperature
dehumidification indicator lamp will off, and the dehumidification relay stops working.
When the measured humidity
Differential Value)
, entering into the status of humidification, indicator lamp of
humidification will on, relay of humidification will work; When the measured humidity
PV≥HS (Humidity Set Value)
humidification stops working.
5.2 Alarm High/Low Limit Setting (AH, AL)
When the measured humidity
measured humidity
PV≤AL
BIII” sound, current value, AH or AL will display on PV screen. The voice of alarm can be
stopped by pressing any key but the status of alarm will be not change until the value of
measured humidity return to the normal range.
5.3 Compressor Delay (PT)
Under dehumidification mode, after power on, if the measured humidity
(Humidity Set Value) + DD
won’t start dehumidification immediately, but waiting for a delay time.
When the time interval between two dehumidification operation
on to dehumidify) is larger than preset delay, the equipment will start dehumidification
immediately; when the time interval between two dehumidification
power on to dehumidify) is less than preset delay, the equipment won’t start
dehumidification until preset delay is satisfied.
Delay time will be calculated right after the moment dehumidification stops.
5.4 Temperature Calibration (CA)
When there is deviation between measured humidity and actual humidity, use humidity
calibration function to align the measured humidity and actual humidity. The corrected
humidity is equal to humidity before calibration plus corrected value (corrected value could
be positive value, 0 or negative value
IHC-200 User Manual
Inkbird Tech. Co., Ltd. www.ink
7
5.1 Temperature Control Range Setting (HS, HD, DD)
When controller works normally, LED displays current measured value of humidity, then
starting the recognition and translation of humidifying and dehumidifying automatically.
When the measured humidity
PV≥HS (Humidity Set Value) + DD (Dehumidification
, entering into the status of dehumidification, indicator lamp of
dehumidification will on, relay of dehumidification will work.
When the dehumidification
indicator light is flickering
, the dehumidifying equipment is being in the status of
protection. When the measured temperature
PV≤HS (Humidity Set Value)
dehumidification indicator lamp will off, and the dehumidification relay stops working.
When the measured humidity
PV≤HS (Humidity Set Value) – HD (Humidification
, entering into the status of humidification, indicator lamp of
humidification will on, relay of humidification will work; When the measured humidity
(Humidity Set Value)
, indicator lamp of humidification will off, relay of
s working.
5.2 Alarm High/Low Limit Setting (AH, AL)
When the measured humidity
PV≥AH (Alarm High Humidity Set Value)
PV≤AL (Alarm High Humidity Set Value)
, alarm with the “BI
BIII” sound, current value, AH or AL will display on PV screen. The voice of alarm can be
stopped by pressing any key but the status of alarm will be not change until the value of
measured humidity return to the normal range.
Compressor Delay (PT)
Under dehumidification mode, after power on, if the measured humidity
(Humidity Set Value) + DD (Dehumidification Differential Value)
won’t start dehumidification immediately, but waiting for a delay time.
the time interval between two dehumidification operation (or the time from power
on to dehumidify) is larger than preset delay, the equipment will start dehumidification
immediately; when the time interval between two dehumidification (or the time from
er on to dehumidify) is less than preset delay, the equipment won’t start
dehumidification until preset delay is satisfied.
Delay time will be calculated right after the moment dehumidification stops.
5.4 Temperature Calibration (CA)
tion between measured humidity and actual humidity, use humidity
calibration function to align the measured humidity and actual humidity. The corrected
humidity is equal to humidity before calibration plus corrected value (corrected value could
value, 0 or negative value
)
.
200 User Manual
Inkbird Tech. Co., Ltd. www.ink-bird.com
When controller works normally, LED displays current measured value of humidity, then
starting the recognition and translation of humidifying and dehumidifying automatically.
(Dehumidification
, entering into the status of dehumidification, indicator lamp of
When the dehumidification
, the dehumidifying equipment is being in the status of delay
(Humidity Set Value)
, the
dehumidification indicator lamp will off, and the dehumidification relay stops working.
(Humidification
, entering into the status of humidification, indicator lamp of
humidification will on, relay of humidification will work; When the measured humidity
, indicator lamp of humidification will off, relay of
(Alarm High Humidity Set Value)
or the
, alarm with the “BI-BI-
BIII” sound, current value, AH or AL will display on PV screen. The voice of alarm can be
stopped by pressing any key but the status of alarm will be not change until the value of
Under dehumidification mode, after power on, if the measured humidity
PV≥HS
(Dehumidification Differential Value)
, the equipment
(or the time from power
on to dehumidify) is larger than preset delay, the equipment will start dehumidification
(or the time from
er on to dehumidify) is less than preset delay, the equipment won’t start
Delay time will be calculated right after the moment dehumidification stops.
tion between measured humidity and actual humidity, use humidity
calibration function to align the measured humidity and actual humidity. The corrected
humidity is equal to humidity before calibration plus corrected value (corrected value could