5.1 Temperature Control Range Setting (HS, HD, DD)

When  controller  works  normally,  LED  displays  current  measured  value  of  humidity,  then 

starting the recognition and translation of humidifying and dehumidifying automatically. 

When the measured humidity 

Differential  Value)

,  entering  into  the  status  of  dehumidification,  indicator  lamp  of 

dehumidification will on, relay of dehumidification will work. 

indicator  light  is  flickering

protection.  When  the  measured  temperature 

dehumidification indicator lamp will off, and the dehumidification relay stops working.

 

When  the  measured  humidity 

Differential  Value)

,  entering  into  the  status  of  humidification,  indicator  lamp  of 

humidification  will  on,  relay  of  humidification  will  work;  When  the  measured  humidity 

PV≥HS  (Humidity  Set  Value)

humidification stops working.

 

5.2 Alarm High/Low Limit Setting (AH, AL)

When  the  measured  humidity 

measured  humidity 

PV≤AL

BIII” sound, current value, AH or AL will display on PV screen. The voice of alarm can be 

stopped by pressing any key but the status of alarm will be not change until the value of 

measured humidity return to the normal range.  

 

5.3 Compressor Delay (PT)

Under  dehumidification  mode,  after  power  on,  if  the  measured  humidity 

(Humidity  Set  Value)  +  DD

won’t start dehumidification immediately, but waiting for a delay time. 

When  the  time  interval  between  two  dehumidification  operation

on  to  dehumidify)  is  larger  than  preset  delay,  the  equipment  will  start  dehumidification 

immediately;  when  the  time  interval  between  two  dehumidification

power  on  to  dehumidify)  is  less  than  preset  delay,  the  equipment  won’t  start 

dehumidification until preset delay is satisfied. 

Delay time will be calculated right after the moment dehumidification stops. 

 

5.4 Temperature Calibration (CA)

When  there  is  deviation  between  measured  humidity  and  actual  humidity,  use  humidity 

calibration  function  to  align  the  measured  humidity  and  actual  humidity.  The  corrected 

humidity is equal to humidity before calibration plus corrected value (corrected value could 

be positive value, 0 or negative value

 

 

 

 

 

IHC-200 User Manual

Inkbird Tech. Co., Ltd.                                                                        www.ink

5.1 Temperature Control Range Setting (HS, HD, DD) 

When  controller  works  normally,  LED  displays  current  measured  value  of  humidity,  then 

starting the recognition and translation of humidifying and dehumidifying automatically. 

When the measured humidity 

PV≥HS  (Humidity  Set  Value)  +  DD  (Dehumidification 

,  entering  into  the  status  of  dehumidification,  indicator  lamp  of 

dehumidification will on, relay of dehumidification will work. 

When  the  dehumidification 

indicator  light  is  flickering

, the dehumidifying equipment is being in the status of 

protection.  When  the  measured  temperature 

PV≤HS  (Humidity  Set  Value)

dehumidification indicator lamp will off, and the dehumidification relay stops working.

When  the  measured  humidity 

PV≤HS  (Humidity  Set  Value)  –  HD  (Humidification 

,  entering  into  the  status  of  humidification,  indicator  lamp  of 

humidification  will  on,  relay  of  humidification  will  work;  When  the  measured  humidity 

(Humidity  Set  Value)

,  indicator  lamp  of  humidification  will  off,  relay  of 

s working. 

5.2 Alarm High/Low Limit Setting (AH, AL) 

When  the  measured  humidity 

PV≥AH  (Alarm  High  Humidity  Set  Value)

PV≤AL  (Alarm  High  Humidity  Set  Value)

,  alarm  with  the  “BI

BIII” sound, current value, AH or AL will display on PV screen. The voice of alarm can be 

stopped by pressing any key but the status of alarm will be not change until the value of 

measured humidity return to the normal range.   

Compressor Delay (PT) 

Under  dehumidification  mode,  after  power  on,  if  the  measured  humidity 

(Humidity  Set  Value)  +  DD  (Dehumidification  Differential  Value)

won’t start dehumidification immediately, but waiting for a delay time. 

 

the  time  interval  between  two  dehumidification  operation  (or  the  time  from  power 

on  to  dehumidify)  is  larger  than  preset  delay,  the  equipment  will  start  dehumidification 

immediately;  when  the  time  interval  between  two  dehumidification  (or  the  time  from 

er  on  to  dehumidify)  is  less  than  preset  delay,  the  equipment  won’t  start 

dehumidification until preset delay is satisfied.  

Delay time will be calculated right after the moment dehumidification stops. 

5.4 Temperature Calibration (CA) 

tion  between  measured  humidity  and  actual  humidity,  use  humidity 

calibration  function  to  align  the  measured  humidity  and  actual  humidity.  The  corrected 

humidity is equal to humidity before calibration plus corrected value (corrected value could 

value, 0 or negative value

200 User Manual

 

Inkbird Tech. Co., Ltd.                                                                        www.ink-bird.com

 

When  controller  works  normally,  LED  displays  current  measured  value  of  humidity,  then 

starting the recognition and translation of humidifying and dehumidifying automatically.  

(Dehumidification 

,  entering  into  the  status  of  dehumidification,  indicator  lamp  of 

When  the  dehumidification 

, the dehumidifying equipment is being in the status of delay 

(Humidity  Set  Value)

,  the 

dehumidification indicator lamp will off, and the dehumidification relay stops working. 

(Humidification 

,  entering  into  the  status  of  humidification,  indicator  lamp  of 

humidification  will  on,  relay  of  humidification  will  work;  When  the  measured  humidity 

,  indicator  lamp  of  humidification  will  off,  relay  of 

(Alarm  High  Humidity  Set  Value)

  or  the 

,  alarm  with  the  “BI-BI-

BIII” sound, current value, AH or AL will display on PV screen. The voice of alarm can be 

stopped by pressing any key but the status of alarm will be not change until the value of 

Under  dehumidification  mode,  after  power  on,  if  the  measured  humidity 

PV≥HS 

(Dehumidification  Differential  Value)

,  the  equipment 

(or  the  time  from  power 

on  to  dehumidify)  is  larger  than  preset  delay,  the  equipment  will  start  dehumidification 

(or  the  time  from 

er  on  to  dehumidify)  is  less  than  preset  delay,  the  equipment  won’t  start 

Delay time will be calculated right after the moment dehumidification stops.  

tion  between  measured  humidity  and  actual  humidity,  use  humidity 

calibration  function  to  align  the  measured  humidity  and  actual  humidity.  The  corrected 

humidity is equal to humidity before calibration plus corrected value (corrected value could 

Содержание IHC-200

Страница 1: ...Tech Co Ltd 2016 Inkbird Tech Co Ltd All rights reserved No part of this document may be reproduced Inkbird has made every effort to ensure that the information contained in this document is complete...

Страница 2: ...3 Compressor Delay PT 5 4 Temperature Calibration CA 6 Error Description 7 Technical Assistance and 7 1 Technical Assistance 7 2 Warranty IHC 200 User Manual Inkbird Tech Co Ltd www ink 2 Contents on...

Страница 3: ...s play plug designed dual LED screens enabling more humanized IHC 200 can control any 265 volt humidifier dehumidifier or fan Switch the modes between humidification and dehumidification automatically...

Страница 4: ...C 200 User Manual Inkbird Tech Co Ltd www ink 4 nstruction Under running mode display current humidity etting mode display menu code When pressing the decrease and increase keys simultaneously it disp...

Страница 5: ...simultaneously the condition of power off all the display and output would be turnoff On the condition of power off press and hold key simultaneously for 1 second to enter the condition of normal mea...

Страница 6: ...bird Tech Co Ltd www ink 6 menu automatically and return to the mode of normal humidity displaying without saving the parameters modification nstruction Function Setting Range Default Humidity Set Val...

Страница 7: ...cator lamp of humidification will on relay of humidification will work When the measured humidity Humidity Set Value indicator lamp of humidification will off relay of s working 5 2 Alarm High Low Lim...

Страница 8: ...ird Tech Co Ltd www ink 8 6 Error Description when humidity sensor is in short circuit or open loop the controller will initiate sensor fault mode and cancel all the actions The buzzer will alarm LED...

Страница 9: ...condition by the original purchaser not transferable against defects caused by INKBIRD s workmanship or materials This warranty is limited to the repair or replacement at INKBIRD s discretion of all...

Отзывы: