IC0020
Conventional resettable manual callpoint
ATTENTION!
IC0020 series manual call points are certified and approved according to EN54-11 -
Manual call points.
Description
IC0020 manual call points are specially designed to operate with
conventional control panels.
The device trigger element and red status LED are located in the
front case of the device. The LED will light up when the device is
activated.
The device details and information regarding the connection
terminals can be found on the label inside the device housing.
The device provides connectors for the resistance jumper. The
position of the jumper defines the alarm resistance, as follows:
The device package contains two fork-end keys which can be used
to open the housing and reset the device
The flush-mount backbox and the protective front plate are
accessory items and must be purchased separately.
Position
Alarm resistance
RL
260 Ohm
RH
660 Ohm
A
Callpoint button - rear
B
Details label
C
Terminals
D
Backbox with fixing screw holes and cable entry
E
Fixed back-locking clips
F
Fixed back-locking clip positions
G
Back-locking backbox clips
H
Back-locking clip positions
I
Reset key slot
J
Protection front plate clips
K
Connectors for the resistance jumper
TECHNICAL SPECIFICATIONS
Operating voltage
10-30 Vdc
Resistance between terminals
“+” and “-” in the event of alarm
260 - 660 Ohm
Operating temperature
-5°C / +40°C
Humidity
(without condensation)
95% RH
Dimensions (HxWxD)
84 x 84 x 45 mm
Weight
126 g
K
C
H
I
J
J
A
B
F
G
D
E
E
F
DCMIIN4AIC0020-R100-20120924
0832-CPD-2053
991j/01