Installation manual
Technical description
15
4.4
Technical specifications
DL1
Power supply
module
green
Indicates that the power-supply unit is
operating (On).
In case of fast blinking the LED
indicates an overheat condition of the
power-supply unit.
In case of slow blinking the LED
indicates an overload of the outputs.
DL2
yellow
Indicates an active mains fault
condition.
In case of slow blinking the LED
indicates an active earth fault condition.
DL3
yellow
Indicates an active battery fault
condition.
Specification
SPS24060S
SPS24160S
AC power
230 V
(-15% / 10%) 50/60 Hz
Maximum current draw 230V
0.5 A
1.1 A
Nominal output voltage
27.6 V
Maximum output current
2.1 A
5.2 A
I
max. a
1.5 A
4 A
I
max. b
1.5 A
4 A
Maximum battery current emission during primary power
failure
1.5 A
4 A
Maximum current for external loads and accessory devices
1.47 A
3.97 A
Maximum battery-charge current
0.6 A
1.2 A
Minimum current (I
min
)
30 mA
Battery specifications
2 x 12V, 7 Ah
2 x 12V, 17 Ah
2 x 12 V/7 Ah YUASA NP-12 FR or similar with case
flame class UL94-V2 or higher
Maximum internal resistance of the batteries (R
i max
)
2.7 Ohm
1 Ohm
Output voltage
from 18 to 27.6V
Battery shutdown tension
19V
Internal fuse of switching power supply module
T 3.15A 250V
Maximum output current ripple
1%
Operating temperature (EN 54-4)
from -5°C to 40°C
Operating temperature (EN 12101-10)
from -5°C to 75°C
Functional class (EN12101-10)
A
Environmental class (EN12101-10)
2
Isolation class
I
Enclosure protection class (EN 60529)
IP42
Dimensions
325 x 325 x 80 mm
497 x 380 x 87 mm
Weight
2.8 Kg
6 Kg
LED
Colour
Signalling
Note