IDS404 INSTALLER MANUAL NO. 700-277-02A ISSUED SEPT 2004 VER 1.02 9
IDS404 INSTALLER MANUAL
!
The operation of the tamper is as follows:
!
If the panel is not armed and a tamper condition occurs, the
siren will not sound but a tamper condition will be reported.
!
If the panel is armed and tamper condition occurs the alarm
will register a zone violation and a tamper condition will be
reported.
!
If a zone is programmed as a priority/ panic zone, a tamper
will register a panic condition as well as a tamper condition,
regardless of whether the panel is armed or not.
4. Zone Expansion
In addition to zone doubling it is possible to expand the number of
zone inputs from 4 to 8 wired zones using the IDS404/8 or alternately
4 wired (original) zones and 4 wireless zones using the IDS404/RF
expansion modules. The additional zones take the place of the
“doubled” zones 1b-4b. In order to use this module a value of
[1]
must
be programmed into location 11. If this option is enabled only 3K3
resistors may be used.
The loop response of these zones is not programmable and is fixed at
0.1 seconds. A 3K3 end-of-line resistor is required for these zones.
For connection of these modules please see the package insert for the
appropriate module.
5. Box Tamper Zone
The tamper zone provided on the main PCB is a non end-of-line zone
i.e. no resistor is required. If this zone is not used it must be disabled
by programming the appropriate value into location 170.
The operation of this zone is as per zone type 11 as programmed for
zones 1-4b and a normally closed tamper switch must be used.
6. Connecting the Telephone Communicator
Refer to Figure 1.
!
The integral communicator has built in lightning protection to
protect it from lightning induced transients. For optimum