ABH2015IQE01_ - Installation and Operation Manual
18.7. Configuring the inverter to work only with the PV array,
without batteries
These inverters can work only from the photovoltaic input, without using the battery input.
INFO
To set up the inverter in this operation mode, see the document “Use and Settings of the ISS 1Play working
only with PV” available at
.
18.8. Configuring the SOC settings
Setting
Description
SOCMAX
Maximum state of charge for charging the batteries from the photovoltaic energy (%).
SOCRED
Maximum state of charge for disconnecting the auxiliary generator (%).
SOCMIN
Minimum state of charge for starting the auxiliary generator (%).
SOCRECX
Reboot state of charge of supply to the consumers using photovoltaic energy (no diesel generator
available) (%).
SOCDESCX
Minimum state of charge to fully discharge the batteries, stopping the supply to the consumers (%).
18.9. Configuring the maximum battery charge power from the
auxiliary genset
This option allows to set the maximum power for charging the batteries from the generator.
To configure this parameter, open
MAIN MENU
>
CONFIGURATION
>
OPERATION MODE
>
MODE
> open the
selected mode>
CHARGING POWER
and specify the maximum power in watts.
When the inverter is connected to the grid or generator, the batteries are charged from the AC source when the
state of charge (SOC) is lower than the set SOC MIN (see
“18.8. Configuring the SOC settings”
18.10. Configuring the AC voltage and rated frequency of the loads
in stand-alone installations
In stand-alone installations these units allow to power the consumption grid with configurable AC voltage and
frequency.
To configure the AC voltage and rated frequency, open the
MAIN MENU
>
CONFIGURATION
>
INVERTER
.
Setting
Description
RMS VOLTAGE
Rated voltage supplying the AC consumers (V).
FREQUENCY
Rated frequency of the consumer output (Hz).
18.11. Configuring the auxiliary generator in stand-alone
installations
In stand-alone installations these inverters can operate with an auxiliary generator that is connected in the event of
a power deficit.
To configure the generator settings, open
MAIN MENU
>
CONFIGURATION
>
GENSET
>
GRID TYPE
>
GENERATOR
and enter the generator settings.
Setting
Description
RATED POWER
Rated power of the diesel generator set (w). With this parameter, the INGECON SUN
STORAGE 1Play estimates the power available for loading the batteries, considering the
consumption of the installation from the diesel generator.
VAC MIN
Minimum AC voltage generated by the diesel generator set (V):
61