ABK2027IQE01_A - Installation and Operation Manual
String13
Current string 13.
String14
Current string 14.
String15
Current string 15.
Total
Energy
Total energy fed through the inverter throughout its useful life.
Time
Total time that the inverter has been feeding the grid.
Connections
Total number of grid connections.
Partial
Energy
Partial energy fed by the inverter.
Time
Partial time that the inverter has been connected to the grid.
Connections
Partial number of grid connections.
19.6.2. Events
This menu shows the events occurring in the inverter.
Alarms
The alarms indicate current events in the inverter that lead to its shut-down.
Alarm
Name
Variable
Code
LED Lighting
Description
Overvoltage
1
0x0001
Orange
This alarm displays when there is an input voltage in the
panel (PV) above the unit's limit.
This voltage is read before the motorized switch,
specifically on the panel input string grouping plates.
Voltage difference
1
0x0002
Orange
The difference between the panel and bus voltage
measurements, both sides of the DC switch, is greater
than the expected limit.
Panel overcurrent
1
0x0004
Red
DC current above the limit allowed by the unit.
AC zero sequence
current
1
0x0008
Red
The instantaneous sum of the AC currents exceeds a
maximum value.
BUS overvoltage
1
0x0010
Red
There is overvoltage exceeding the maximum DC voltage
limit.
Instantaneous AC
overvoltage
1
0x0020
Orange
The instantaneous AC voltage in one of the three phases
exceeds the unit's HW limit.
AC rms voltage or
AC frequency
1
0x0040
0x0200
Orange
The network voltage in one or several phases is outside
of the limits established in the unit's settings for a period
above that defined in the settings. This alarm can be
instantaneous or permanent, depending on the duration
of the fault.
The unit's voltage and frequency relays are configured
according to the limits established in the regulations
applicable to each installation.
Instantaneous AC
overcurrent
1
0x0080
Red
The instantaneous AC current in one of the three phases
exceeds the unit's instantaneous limit.
AC rms overcurrent
1
0x0100
Red
The AC rms current in one of the three phases exceeds
the unit's instantaneous limit.
PWM fault
1
0x0400
Red
There have been multiple faults in the power switches. For
safety reasons, the unit will stand by for an inspection.
133
Display control
Ingeteam
Содержание INGECON SUN 1000TL U B360
Страница 1: ...INGECON SUN PowerMax TL U B 1000 Vdc Installation and Operation Manual...
Страница 22: ...ABK2027IQE01_A Installation and Operation Manual DC supply 22 Unit description Ingeteam...
Страница 176: ...Notes...
Страница 177: ...Notes...
Страница 178: ...Notes...
Страница 180: ...ABK2027IQE01_A 05 2019 Ingeteam Power Technology S A www ingeteam com...