Installation manual
Ingeteam Power Technology, S.A.
A
A
To access these terminals the protective polycarbonate sheet must be removed.
After working on the terminals the polycarbonate guard must be put back into place.
Units with a transformer
Units without a transformer (TL)
AC feed
M8 copper terminal strip
Plate with one M10 copper orifice
Wire gauge as per DIN 46234:
•
1 95 mm
2
cable
•
2 70 mm
2
cables on each side
Wire gauge on each pole:
•
2 240 mm
2
cables
12 Nm torque
47 Nm torque
DC feed
Plate with two M12 copper orifices
Wire gauge on each pole:
•
4 240 mm
2
cables
64 Nm torque
5.5. Synchronización of units
When several Ingecon
®
Sun Power TL units are connected to the same medium voltage transformer, they must be
synchronized.
Care must be taken to ensure the equipment is not live when accessing its interior.
The configuration of PV array voltages should be the same.
MPPTs connected by TL inverters to the same transformer should have the same voltage settings.
To synchronize Ingecon
®
Sun Power TL units, a synchronization signal generator kit (AAS0133) must be added,
capable of synchronizing up to 6 units.
In the following example, 4 Ingecon
®
Sun 100 TL units are synchronized: