Installation
26
RT-SVX46C-EN
•
lists the conductor sizing guidelines that
must be followed when interconnecting the DC binary
output devices and the system components utilizing a
DC analog input/output signal to the unit.
Note:
Resistance in excess of 2.5 ohms per conductor can
cause deviations in the accuracy of the controls.
Note:
Ensure that the wiring between controls and the
unit’s termination point does not exceed two and a
half (2.5) ohms/conductor for the length of the run.
•
Do not run the electrical wires transporting DC signals
in or around conduit housing high voltage wires.
•
Route low voltage wiring per illustrations on page
DC Conductors
Table 4.
Zone sensor module wiring
Distance from Unit to Control Recommended Wire Size
0 - 150 feet
22 gauge
0 - 45.7 m
.33 mm2
151 - 240 feet
20 gauge
46 - 73.1 m
.50 mm2
241 -385 feet
18 gauge
73.5 - 117.3 m
.75 mm2
386 - 610 feet
16 gauge
117.7 - 185.9 m
1.3 mm2
611 - 970 feet
14 gauge
186.2 - 295.7 m
2.0 mm2
Figure 23.
ReliaTel™ options module
Figure 24.
ReliaTel™ relative humidity sensor (enhanced
dehumidification operation)
Figure 25.
ReliaTel™ humidistat (enhanced
dehumidification operation)
J8
TP1
DA COOL
FAN SPD
TP2
DA HEAT
TP3
EXH
FAN
SPC PRESS DB SPC PRESS
J4
J9
J10
J11
J12
J3
TP4
TP5
DEHUMID
TB1
TB2
J6
J7
J5
J1
J2
Low Voltage
Terminal Block
NLTB
NLTB
Located on Front
of Rooftop Unit
Control Box
Relative Humidity
Sensor
(Field Supplied)
Field Supplied
Cable
NLTB
12
13
15
17
19
14
16
18
R.H.+
R.H.-
Low Voltage
Terminal Block
Humidistat
(Field Supplied)
Field Supplied
Wire
COM
HI
LTB
Located on Front
of Rooftop Unit
Control Box
LTB
7
9
11
13
8
10
12
14