S9V2-SF-2A-EN
59
DEFINITION:
This fault is generated when the HP or
OEM ID of the blower motor does not
match the value that is programmed on
the Personality Module
13 Fault Code
Does the model &
serial number of
the PM match the
nameplate?
Disconnect electrical
power to furnace.
Replace PM with the
correct model/serial
NO
Remove blower
ves!bule panel to
gain access to
blower motor
YES
Does the blower
motor HP match
the nameplate?
Replace motor with
correct HP
NO
Replace motor
YES
DEFINITION:
This fault is generated when the PM is
missing and the onboard informaon
cannot be read
14 Fault Code
Disconnect power
Is PM installed
and fully seated?
Install and/or fully
seat
NO
Possible causes:
PM not programmed
Faulty IFC
YES