ingersollrandproducts.com
15
PROBLEM
SYMPTOM(S)
POSSIBLE CaUSE
CORRECTIVE aCTION
Apparent controller
display malfunction
Display Blank
Blown Fuse
Check Fuses
Board Failure
Contact your local distributor
for further assistance.
Unrealistic temperature
displayed
Probe loose, off connection or
defective probe
Inspect probe cable and
terminal connection Replace
probe
Erratic or inaccurate
temperature readings
Probe not completely in
thermal well
Inspect probe and check
readings against independent
source (eg. temperature
analyzer/pyrometer/ice bath)
both in temperature well and to
ambient
Defective probe
Replace probe
Unrealistic pressure
displayed
Transducer loose, off
connection or defective
transducer
Inspect transducer cable and
terminal connection
Replace transducer
High pressure drop
across dryer
Outlet pressure
substantially lower than
inlet pressure System
operating temperature is
above 32°F
Inlet and outlet valves not
completely open
Open valves
Inlet and outlet filters blocked
up.
Change filter elements
Outlet pressure
substantially lower than
inlet pressure System
operating temperature is
below 32°F
Compressor relay / contactor
stuck.
Replace relay / contactor.
Microprocessor Control relay
bad
Replace relay
Probe not completely in
thermal well
Inspect probe and check
readings against independent
source (eg. temperature
analyzer/pyrometer/ice bath)
both in exchanger well and to
ambient
Problem persists
Turn dryer off and consult your
local distributor for further
assistance
Condensate drain
does not fire
Check installation is in
accordance with this manual.
Revise installation accordingly.
Inlet / outlet pipe internal
diameter too small causing
air-lock or back pressure.
Replace with larger diameter
piping.
Excessive use of bends / elbows
in inlet / outlet pipe work
causing air-lock/ back pressure.
Reduce the amount of bends
and elbows.
Outlet pipe too long / too
high causing back pressure.
Reconfigure condensate piping.
More than one condensate
source connected providing
alternative path for
condensate.
Reroute condensate to
eliminate secondary
path. Install check valves as
required.
10.0 TROUBLESHOOTINg