b) Stop the dryer 2 minutes after shutting down the air compressor or interrupting

the air flow to the dryer.

Avoid allowing compressed air to enter the dryer when the dryer is

switched off or when it is in an alarm situation which stops the refrigeration

compressor.

3.4 Operation

S

The dryer operates automatically. It is factory set for a dew point of 50

˚

F (10

˚

C)

and therefore requires no further calibration.

S

Do not exceed the machine’s design limits, by---pass excess air flow and check the

unit model and/or installation.

S

For maximum performance from your dryer, follow the maintenance schedule de-

scribed in Chapter 4.

S

The sound pressure level recorded for these dryers 40 inch (at 1 metre) from the

machine in free field conditions is less then 50 dB(A) (

models DS15

--

H

), 55 dB(A)

(

models DS25

--

H---DS100

--

H

)

Fig. 6 shows the Dryer’s refrigeration and air circuits.

N.B.:

In the event of aftercooler fan malfunction leading to an increase in the tem-

perature within the filter, to above 149

˚

F (65

˚

C), check the integrity of the filter’s

element and drain and substitute these components if necessary.

4 Maintenance

Before accessing live electrical parts

, disconnect the power supply to the

dryer using disconnect switch QS or disconnect the cable connections.

SAFETY DEVICES

SK

overload protector

HP

high pressure switch

(installed on models DS50

--

H---DS100

--

H)

COMPRESSOR TYPE

HERMETIC, PISTON

(single phase)

N.B.:

Always use original spares supplied by the manufacturer.

Failure to do so renders the manufacturer not liable for incorrect unit operation.

4.1 Preventive maintenance

For optimum performance from your dryer follow the periodic maintenance sched-

ule described below.

WEEKLY

CONDENATE DRAIN

WEEKLY

CONDENATE DRAIN

Verify that the condensate drain is draining correctly.

MONTHLY

COMPRESSOR

Make sure the compressor head temperature is below 200

˚

F (93

˚

C)

MONTHLY

Make sure the compressor head temperature is below 200 F (93 C)

when running. If this is not the case consult Chapter 7.

EVERY 4 MONTHS

REFRIGERANT CONDENSER AND AFTERCOOLER

Remove any dust from the condenser/aftercooler fins.

COMPRESSOR

Make sure compressor power consumption complies with data plate

specifications.

EVERY 4 MONTHS

specifications.

AFTERCOOLER FAN MOTOR

S

Check that the fan rotates freely without any abnormal noise.

S

Make sure fan power consumption complies with the specifica-

tions on the fan’s data plate.

YEARLY

AFTERCOOLER

If necessary (coil blocked) remove the fan and clean the coil in the

opposite direction to the air flow using a high pressure water jet (this

operation must be performed by a technician to avoid damage).

FILTER ELEMENT

Replace the filter element (see para. 4.2)

CONDENSATE DRAIN

Completely disassemble the drain and clean all its components (see

Fig. 9 or separate manual, according to installed drain type).

4.2 Substituting an exhausted element

(Fig. 9)

N.B.:

Don’t touch the element sock with your bare hands; use gloves.

a) Shut off or by---pass air supply to dryer.
b) Depressurise filter using manual or automatic drain valve (18). Leave valve open.
c) Unscrew (anticlockwise) filter body from head.
d) Unscrew and remove element (17).
e) Clean inside of filter if necessary.

Содержание DS100-H

Страница 1: ... 272716 DATE 06 11 2002 ISSUE 2 CPN 85616902 User manual Page 1 Manuel d utilisation Page 7 Manual de uso Página 13 Manual do utilizador Página 19 Benutzerhandbuch Seite 25 DS15 H DS100 H refrigeration dryer 60Hz ...

Страница 2: ...purpose for which it is intended Improper use of the machine absolves the manufacturer from all liability This manual has been compiled to help the final user perform just those oper ations which do not require removal of the panels All other operations which involve the removal of covers from instruments or electrical circuit breakers using special tools must only be carried out by trained person...

Страница 3: ...machine as close as possible to the installation site 1 4 Storage If stored the packaged units must be kept inside protected from humidity direct sunlight and rain Moreover although stacking is permitted the maximum weight must not be more than the value shown on the packaging 1 5 Inspection On receipt of the machine make sure it has incurred no damage during transit If any damage is detected prom...

Страница 4: ...s or chemical products which may damage the compressor or components inside the dryer Take particular care with sulphur ammonia chlorine and installations in marine environments For further advice or assistance consult the manufacturer 2 2 Electrical connection see Fig 5 Fig 10 The dryer is supplied with a 3 x AWG16 power cable complete with plug Install an overcurrent and earth leakage circuit br...

Страница 5: ...facturer Failure to do so renders the manufacturer not liable for incorrect unit operation 4 1 Preventive maintenance For optimum performance from your dryer follow the periodic maintenance sched ule described below WEEKLY CONDENATE DRAIN WEEKLY CONDENATE DRAIN Verify that the condensate drain is draining correctly MONTHLY COMPRESSOR Makesure thecompressor headtemperature isbelow 200 F 93 C MONTHL...

Страница 6: ...gum synthetic compressor steel copper aluminium oil condensator steel copper aluminium refrigerant R134a valve brass electrical cable copper PVC 4 4 Refrigerant leaks in the refrigeration circuit FOREWORD The unit is delivered in perfect working order already charged as specified in Fig 5 Refrigerant leaks may be identifiedby trippingof thecompressor overloadprotector SK IFALEAKISDETECTED INTHE RE...

Страница 7: ...does not work Repair fan Ambient temperature over 115 F 46 C Reduce temperature Compressor components perished Repair or replace com pressor Seek exter nal assis tance Compressor winding insulation partially perished compressor too hot Low current consumption Lack of refrigerant Recharge Condenser dirty cooling air outlet too hot Clean condenser Fan does not work Low evaporation pressure by pass a...

Страница 8: ...1 CPN 85616902 DS15 H DS100 H Fig 1 Installation suggested compressor by pass oil water separator receiver Aftercooler filter to compressed air ring main Dryer filter high inlet temperature dryer package ...

Страница 9: ...32 CPN 85616902 DS15 H DS100 H Fig 2 Safety and description labels on dryer a e d f f f c b b g ...

Страница 10: ...ge caused by a wrong refrigerant recharge will not be under warranty h Internal dryer b REMEMBER TO CHANGE YOUR FILTER ELEMENT element installed on REMEMBER TO CHANGE YOUR FILTER ELEMENT element installed on We strongly recommend filter elements be changed once a year or after 8000 working hours whichever comes first Only use genuine Ingersoll Rand elements Refer to User Manual for correct replace...

Страница 11: ...34 CPN 85616902 DS15 H DS100 H Fig 4 Overall dimensions O B H J K I C E G F L A filter separator discharge tube supply cable air inlet air outlet D M N condensate drain tube ...

Страница 12: ...3 7 2 22 5 152 102 30 50 22 DS75 H 27 6 700 47 7 1212 13 9 352 25 6 650 140 3 3 83 5 7 2 183 5 DS100 H 700 1212 352 650 83 5 183 5 Fig 5 Technical data model weight refrigerant charge R134a F L A A air max air ambient temperature max air model kg lb gr oz 115V 1 60Hz air connections inlet temp min max max air pressure DS15 H 25 55 130 4 59 3 7 3 8 NPT F DS25 H 42 93 195 6 88 5 6 1 2 NPT F DS35 H 4...

Страница 13: ...ftercooler fan motor 16 aftercooler coil 17 filter separator AIR OUTLET AIR INLET condensate condensate drain 17 drain 16 15 11 10 5 1 7 8 12 2 3 13 only for model DS50 H DS100 H Fig 7 Calibration MODEL SETTING COMPONENT DS15 H DS100 H 31 9 PSI 0 15 0 Automatic expansion valve 7 DS15 H DS100 H 2 2 bar 0 1 0 OUTLET INLET DS15 H DS100 H START 113 F 45 C STOP 104 F 40 C Fan condensing temperature swi...

Страница 14: ...6829 85616837 16 85616845 85616852 85616860 17 85616878 85616886 85616894 18 89327944 CONDENSATE DRAIN A 89327936 B 89327951 Fig 9 Parts 1 compressor 2 refrigerant condenser 3 fan motor 4 5 10 evaporator separator air air heat exchanger 7 expansion automatic valve 8 refrigerant filter 11 dew point thermometer 12 fan condensing temperature switch A B Float condensate drain 4 5 10 2 3 12 8 7 condens...

Страница 15: ...UIPMENT R2 SK 3 1 1 N QS S1 R1 TV R1 R1 C MC R S S 1 2 KA C1 R EV1 S1 HL L 115V 1 60Hz C2 only for model DS100 H black brown GND blue d d GND L1 L2 L1 L2 GND EV2 R1 S1 QF Inn 0 03A RECOMMENDED and generally demanded by law by installer R3 HP only for model DS50 H DS100 H p ...

Страница 16: ...T element installed on We strongly recommend filter elements be changed once a year or after 8000 working hours whichever comes first Only use genuine Ingersoll Rand elements Refer to User Manual for correct replacement element c QUALITY CHECKED INSPECTOR N 302 d Air inlet e Air outlet f Condensate drain connection g WARNING Risk of electric shock can cause injury or death Disconnect all remote el...

Отзывы: