Ingersoll-Rand D1020IN Скачать руководство пользователя страница 6

Non-cycling Refrigerated Dryer  

 

 

MODELS D340IN, D40IN, D510IN, D680IN, D850IN, D100IN, D1190IN, D1360IN

 

http://air.ingersollrand.com

7.0 PRINCIPLES OF OPERATION

7.1 INTRODUCTION

Ingersoll Rand non-cycling dryers remove moisture, oil vapor 

and other contaminants from compressed air by cooling the 

air temperature to 36 deg.F (. deg.C).  This cooling process 

condenses the contaminants into liquid droplets which can 

then be easily removed from the air.  The major systems of 

the dryers that contribute to its operation are the following: 

Air System, Moisture Removal System, Refrigeration System 

and the Controls System.  The following paragraphs describe 

each of the systems in greater detail.

7.2 AIR SYSTEM

This system consists of the dryer components which are 

in contact with the compressed air.  Referring to Figure 

1 and following the bold “AIR FLOW” path indication, hot 

saturated air from the air compressor enters the precooler/

reheater where the air temperature is reduced prior to 

entering the chiller by the cool air exiting the air/moisture 

separator.  This precooling allows for the use of a smaller 

refrigeration system.  The air then goes into the chiller 

section where it is further cooled to the desired dew point 

through direct heat transfer with evaporating refrigerant.  

The air continues to the separator where the moisture is 

removed, thereby allowing the cool, dry air to return to the 

precooler/reheater.  As the air passes through the precooler/

reheater the air temperature is elevated by the warm, wet 

inlet air.  The air exiting the reheater portion of the dryer 

should be approximately 15-0 deg.F lower than the inlet air 

temperature based on standard conditions at full rated flow.

7.3 MOISTURE REMOVAL SYSTEM

Liquid droplets are removed from the air stream in the 

separator.  As the air and liquid mixture passes through the 

separator it spins, slows down and then changes direction.  

This causes condensate to fall out of the air stream and 

collect in the bottom of the separator.  The collected liquid is 

removed from the separator by a timed electric drain which 

is controlled by the Controller.
The Drain Open time and Drain Closed time are accessed 

by depressing the appropriate button and using the up and 

down arrows to change the value.  The Drain Open value is 

seconds; the Drain Closed value is minutes.

To obtain the optimum time values for operation of 

the electric drain valve, set the drain closed time to 

five minutes and the open time to ten seconds.
After running the unit under full rated flow for 

approximately 30 minutes, verify that when the 

electric drain opens, all of the accumulated liquid is 

discharged and then followed by a small burst of air.
If a small amount of liquid and a large amount of air is 

discharged, decrease the on-time setting or increase 

the off-time setting.  If there is all liquid and no air 

has been discharged, increase the on-time setting or 

decrease the off-time setting.
The on/off-time settings will vary accordingly to 

seasonal conditions.  During the summer when more 

moisture is present in the air system, a shorter on-

time that increases the valve opening frequency is 

required.  A longer off-time may be used during the 

winter months when moisture levels are lower.

7.4 REFRIGERATION SYSTEM

The Refrigeration System consists of all the components 

which handle refrigerant R-404A.  This is a hermetically 

sealed closed-loop system.  Referring to Figure 1 and 

following the dot-dash “REFRIGERANT FLOW” path 

indication, refrigerant is shown leaving the chiller evaporator 

section, which in the process of removing heat is changed 

from a low pressure liquid to a low pressure gas.  This 

gas enters the suction side of the compressor where it is 

compressed into a high pressure gas.  The high pressure gas 

is cooled in the condenser section becoming a high pressure 

liquid.  It then goes through a permanent filter-dryer that 

ensures the refrigerant system is free of contaminants.  A 

small diameter capillary tube or expansion valve meters 

the refrigerant into the chiller’s evaporator.  The pressure 

is reduced upon entering the chiller evaporator where it 

removes heat from the air system.  When there are low loads 

(low air flow rate or low inlet temperature), a hot gas valve 

by-passes the condenser and throttling device.  This valve 

maintains a minimum evaporator pressure of 76 psig, which 

corresponds to a chiller temperature of 34 deg.F, to prevent 

freeze-up.

Содержание D1020IN

Страница 1: ...ERATED DRYER 200 800 SCFM Ensure that the operator reads and understands the decals and consults the manuals before maintenance or operation Ensure that the Operation and Maintenance manual is not rem...

Страница 2: ...ALARM 9 7 5 3 ADJUSTING SET POINTS 9 7 5 4 ALARMS AND THEIR FUNCTIONS 10 7 5 5 ALERT MESSAGES 10 7 5 6 START MODES 10 7 5 6 1 Manual Mode 10 7 5 6 2 Auto Restart 10 contents page 8 0 INSTALLATION AND...

Страница 3: ...ny repairs replacements or adjustments to the Equipment or any costs of labor performed by the Purchaser or others without Company s prior written approval The effects of corrosion erosion and normal...

Страница 4: ...y result in minor or moderate injury NOTICE Notice is used to indicate a statement of company policy as the message relates directly or indirectly to the safety of personnel or protection of property...

Страница 5: ...INCOMING LINEVOLTAGE 200 240VAC 1PH 50 60HZ BY OTHERS REFERTO UNIT NAMEPLATE FOR POWER REQUIREMENTS 200 240VAC 1 PH 1 2 3 4 5 6 GRN RED WHT G L1 L2 BLK L3 FACTORY WIRING INCOMING LINEVOLTAGE 200 575V...

Страница 6: ...ller The Drain Open time and Drain Closed time are accessed by depressing the appropriate button and using the up and down arrows to change the value The Drain Open value is seconds the Drain Closed v...

Страница 7: ...LET AIR INLET PRECOOLER REHEATER CONDENSER AIR COOLED COMPRESSOR REFRIG FAN MOTOR PROCESS INSTRUMENTATION DIAGRAM D340IN D680IN 550140 figure 1 BYPASS VALVE HOT GAS LEGEND CONDENSATE DRAIN S REFRIG R4...

Страница 8: ...te the following Turning the adjustment screw clockwise raises suction pressure and exchanger temperature Turning the adjustment screw counter clockwise reduces suction pressure and exchanger temperat...

Страница 9: ...operating DEGREES F DEGREES C Indicates the temperature units of measure HIGH TEMP ALARM Indicates that the exchanger temperature has risen above the High Temperature Alarm set point LOW TEMP ALARM W...

Страница 10: ...d to continuous or long term exposure Note that this alarm will shut down the dryer after a response time delay This alarm will activate the remote alarm contact and reset automatically once the alarm...

Страница 11: ...e cabinet 8 2 PIPING AND VALVES Install piping fittings and accessories as required for specific site conditions and requirements Figure 3 indicates a typical piping arrangement for a refrigerated dry...

Страница 12: ...rical configurations All customer connections can be made at the terminal connections located in the customer electrical connection box on the rear of the dryer Refer to General Arrangement and approp...

Страница 13: ...cur Be especially careful to clean the center brass orifice and the rubber gasket orifice on the orifice cup with a straight pin Reassemble all drain components after the drain has been cleaned and in...

Страница 14: ...nd outlet temperatures are the same No power to the dryer Check power supply and fuses circuit breakers High suction pressure Check and clean condenser Refrigerant leak Check suction pressure gauge if...

Страница 15: ...pen Open valves Inlet and outlet filters blocked up Change filter elements Outlet pressure substantially lower than inlet pressure System operating temperature is below 32 F Compressor relay contactor...

Страница 16: ...16 Non cycling Refrigerated Dryer MODELS D340IN D420IN D510IN D680IN D850IN D1020IN D1190IN D1360IN http air ingersollrand com 11 0 WIRING DIAGRAM...

Страница 17: ...ng Refrigerated Dryer 17 MODELS D340IN D420IN D510IN D680IN D850IN D1020IN D1190IN D1360IN http air ingersollrand com WIRING DIAGRAM D850IN D1020IN W COMPUSTAT 208 230 460 575V 3 60 550136 11 0 WIRING...

Страница 18: ...cling Refrigerated Dryer MODELS D340IN D420IN D510IN D680IN D850IN D1020IN D1190IN D1360IN http air ingersollrand com WIRING DIAGRAM D1190IN D1360IN W COMPUSTAT 208 230 460 575V 3 60 550137 11 0 WIRIN...

Страница 19: ...n cycling Refrigerated Dryer 19 MODELS D340IN D420IN D510IN D680IN D850IN D1020IN D1190IN D1360IN http air ingersollrand com 11 0 WIRING DIAGRAM WIRING DIAGRAM D340INA AIRCOOLED 230 1 60 220 1 50 5501...

Страница 20: ...N MODELS CUSTOMER ELECTRICAL CONNECTIONS ACCESS PANEL FILTER LOCATION NOT SHOWN MICROPROCESSOR CONTROL SEE TECHNICAL MANUAL FOR OPERATION DETAILS CONDENSER AIIR DISCHARGE CONDENSER AIR INLET CONDENSER...

Страница 21: ...CONTROL SEE TECHNICAL MANUAL FOR OPERATION DETAILS 1 4 O D NYLON DRAIN TUBE CUSTOMER ELECTRICAL CONNECTION BOX CONDENSER AIR DISCHARGE CONDENSER AIR DISCHARGE CONDENSER AIR INLET HOT GAS BYPASS VALVE...

Страница 22: ...KVA EXCEPT D340IN 230 1 60 1 23390925 VALVE HOT GAS D340IN D420IN D510IN 1 23390933 VALVE HOT GAS D680IN 1 Models D850IN D1360IN CCN DESCRIPTION QTY UNIT SPARES 1 2 3 38052197 BOARD CONTROL 1 1 1 1 3...

Страница 23: ...3 7 11 2 2 5 10 1 1 6 0 5 1 2 D420IN 230 3 60 340 154 3 8 1 59 12 7 3 11 2 4 8 25 1 1 6 1 3 D420IN 575 3 60 340 154 3 8 1 59 5 3 11 2 2 5 10 1 1 6 0 5 1 2 D510IN 460 3 60 375 170 4 0 1 81 8 5 1 11 2...

Страница 24: ...overhaul your equipment to factory specifications using only genuine Ingersoll Rand parts A SUBSTITUTE IS NOT A REPLACEMENT Ensure you get peak performance and longevity out of your Ingersoll Rand pro...

Отзывы: