Sequence of Operation

RT-SVF28F-EN

17

satisfy the cooling requirement, the thermostat closesY2.

The compressor contactor (CC2) coil is energized provided

the low pressure control (LPC2), high pressure control
(HPC2) and discharge line thermostat (TDL 2) are closed.

When the (CC2) contacts close, compressor (CPR2) starts.

Electromechanical Control Evaporator Fan
Operation (for Gas Units)

When the thermostat fan selection switch is set to the

“Auto” position, the Ignition Module (IGN) energizes the

indoor fan relay (F) approximately 1 second after
energizing the compressor contactor coil (CC1) in the
cooling mode. In the heating mode, the Ignition Module
(IGN) energizes the indoor fan relay (F) coil approximately
45 second after gas ignition. Closing indoor fan relay (F)
coil starts the indoor fan motor (IDM). The (IGN) de-
energizes the fan relay (F) approximately 80 seconds after
the cooling requirement has been satisfied to enhance unit
efficiency.

When the heating cycle is terminated, the indoor fan relay

(F) coil is de-energized approximately 90 seconds after the
heating requirement.

When the thermostat fan selection switch is set to the “On”

position, the (IGN) keeps the indoor fan relay coil (F)
energized for continuous fan motor operation.

Electromechanical Evaporator Fan
Operation (for Cooling Only Units)

When the thermostat fan selection switch is set to the

“Auto” position, the thermostat energizes the indoor fan

relay coil (F) to start the indoor fan motor (IDM). The fan
relay (F) de-energizes after the cooling requirement has
been satisfied. When the heating cycle is terminated, the
indoor fan relay (F) coil is de-energized with heater
contactors.

When the thermostat fan selection switch is set to the “On”

position, the thermostat keeps the indoor fan relay coil (F)
energized for continuous fan motor operation.

Economizer Set-Up

Adjusting the minimum position potentiometer located on

the unit economizer actuator (ECA) sets the required
amount of ventilation air.

Ambient temperature is controlling the economizing cycle

by sensing the outside air dry bulb temperature.

Table 18,

p. 14

lists the selectable dry bulb values by potentiometer

setting.

Electromechanical Control Cooling with
an Economizer

The economizer is utilized to control the zone temperature

providing the outside air conditions are suitable. Outside
air is drawn into the unit through modulating dampers.

When cooling is required and economizing is possible, the

unit economizer actuator (ECA) opens the economizer

damper. The ECA continues to modulate the economizer
damper open/closed to keep the mixed air temperature in
the 50ºF to 55ºF range.

The thermostat will close the Y2 contacts to turn on

contactor (CC1) if mechanical cooling is required.

If economizing is not possible, the ECA drives the damper
to the minimum position setpoint when the indoor fan
relay (F) is energized and allows mechanical cooling
operation.

Electromechanical Control Heating
Operation (for Cooling Only Units)

When the system switch is set to the “Heat” position and

the zone temperature falls below the heating setpoint, the
thermostat closes W1 contacts the first stage electric heat
contactor (AH or AH & CH) is energized. If the first stage of
electric heat can not satisfy the heating requirement, the
thermostat closes W2.

When theW2 contacts close, the second stage electric heat

contactor (BH) is energized, if applicable. The thermostat
cycles both the first and second stages of heat “On” and

“Off” as required to maintain the zone temperature

setpoint.

Electromechanical Control Heating
Operation (for Gas Units)

When the system switch is set to the “Heat” position and

the zone temperature falls below the heating setpoint, the
Ignition module (IGN) initiates a heat cycle.

Ignition Module Low, Medium and
High Heat

Two-stage (IGN) runs self-check (including verification that

the gas valve is de-energized). (IGN) checks the high-limit
switches (TC01 & TC02) for normally closed contacts, the
pressure switch (PS) for normally open contacts, and the
flame rollout (FR) switch for continuity. (IGN) energizes
inducer blower on high speed to check pressure switch
closure.

If the pressure switch is closed, the inducer blower starts
a 20 second pre-purge (15 seconds on high speed followed
by 5 seconds on low speed).

If the pressure switch (PS) is still open, the inducer blower
will continue to be energized on high speed until pressure
switch closure.

After pre-purge completes, the (IGN) energizes the first

stage of the gas valve, initiates spark for 2 seconds
minimum, 7 seconds maximum (ignition trial) and detects
flame and de-energizes spark. From this point, a fixed 45
second indoor blower delay on timing starts.

After the indoor blower delay on is completed, the (IGN)

energizes the indoor blower. The (IGN) enters a normal
operating loop where all inputs are continuously
monitored. If the first stage of gas heat can not satisfy the
heating requirement, the thermostat closes W2.The (IGN)

Содержание Precedent TSC120F Series

Страница 1: ...ng Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on th...

Страница 2: ...ates a potentially hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could res...

Страница 3: ...mission Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change Trademarks All trademarks...

Страница 4: ...nits 14 ReliaTel Control Heating Operation for Gas Units 14 Ignition Module 14 Drain Pan Condensate Overflow Switch Op tional 15 VAV Units Only Sequence of Operation 15 Supply Air Pressure Control 15...

Страница 5: ...Mid Heat Input Btu High Heat Input Btu 2 2 2 Gas Supply Line Pressure Natural minimum maximum LP minimum maximum 4 5 14 0 11 0 14 0 Gas Connection Pipe Size in Low Heat Mid Heat High Heat 3 4 3 4 3 4...

Страница 6: ...ta will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table 3 Direct drive evaporator fan performance 10 tons standard efficiency TSC120F3 4 W...

Страница 7: ...abular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table 5 Direct drive evaporator fan performance 10 tons standard efficiency with...

Страница 8: ...n in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table 7 Direct drive evaporator fan performance 10 tons standard effic...

Страница 9: ...f 10 12 W Unit Model Octave Center Frequency Overall Tons Number 63 125 250 500 1000 2000 4000 8000 dBA 10 T YSC120F 91 86 90 86 82 78 73 67 88 Note Tests follow AHRI270 95 Table 11 Static pressure dr...

Страница 10: ...0 Volts Three Phase 10 TSC120F4 BAYHTRA418 18 0 1 32 5 35 10 TSC120F4 BAYHTRA427 27 0 2 46 0 50 10 TSC120F4 BAYHTRA436 36 0 2 59 5 60 10 TSC120F4 BAYHTRA454 54 0 2 70 4 80 575 Volts Three Phase 10 TSC...

Страница 11: ...0 T YSC120F4 Direct Drive 1 460 3 3 60 4 30 10 T YSC120FW a Direct Drive 1 460 3 3 60 4 30 a T YSC120FW utilize 460V Evaporator Motors Table 16 Electrical characteristics power exhaust cooling and gas...

Страница 12: ...nsed location Three Stages of Cooling1 When the unit is configured for three stage cooling and the system switch is set to the cool position and the zone temperaturerisesabovethecoolingsetpointcontrol...

Страница 13: ...ller i e zone sensor or thermostat while in reheat the reheat valve is de energized and the compressor continues to run or the heat is turned on The 3 minute compressor on and off times are still acti...

Страница 14: ...1 AmbientTemperature controlling the economizing cycle by sensing the outside air dry bulb temperature Table 18 p 14 lists the selectable dry bulb values by potentiometer setting 2 Reference Enthalpy...

Страница 15: ...gnostic system through the zone sensor or Building Automation System BAS will be required Cycling unit power will also clear the fault VAV Units Only Sequence of Operation Supply Air Pressure Control...

Страница 16: ...r lowering energy usage The user defined parameters are the same as for outdoor air reset Logic for zone or return reset control is the same except that the origins of the temperature inputs are the z...

Страница 17: ...dampers When cooling is required and economizing is possible the unit economizer actuator ECA opens the economizer damper The ECA continues to modulate the economizer damper open closed to keep the mi...

Страница 18: ...reaches the trip point the COF relay energizes and opens the 24VAC control circuit which disables the unit Once the 24VAC control circuit is opened a delay timer will prevent unit start up for three...

Страница 19: ...ient 95F OD Ambient 105F OD Ambient 115F OD Ambient 68 57F ID DB WB 74 62F ID DB WB 80 67F ID DB WB 86 72F ID DB WB Figure 2 T YSC120F pressure curve system 2 150 200 250 300 350 400 450 500 550 600 6...

Страница 20: ...20 RT SVF28F EN Subcooling Charging Chart Figure 3 T YSC120F subcooling charging chart PSIG SYS 1 SYS 2...

Страница 21: ...RT SVF28F EN 21 Refrigerant Circuit Figure 4 T YSC120F...

Страница 22: ......

Страница 23: ......

Страница 24: ...vanced controls and HVAC systems comprehensive building services and parts For more information visit www IRCO com The manufacturer has a policy of continuous product and product data improvement and...

Отзывы: