Страница 1: ...or property damage Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance IF YOU SMELL GAS Extinguish any open flame Don t touch any electrical switch or telephone Go to a neighbor and call your gas supplier immediately Follow any and all instruction from your gas supplier If your gas supplier is not available call the fire department FIE...
Страница 2: ...GP M45J CX 01A 4005 CB 4002 CB Manual RD JUN 2008 R L 02A BA ...
Страница 3: ...rio USA 30830 L4W 2A6 Phone 706 554 6191 Phone 905 712 4766 Fax 706 554 9390 Fax 905 712 8336 e mail csr schwankgroup com www patioschwank com e mail csr infrasave com www infrasave com TABLE OF CONTENTS TOPIC PAGE NUMBER 1 GENERAL 1 2 INSTALLATION REQUIREMENTS 1 3 GAS SUPPLY 1 3 1 GAS REQUIREMENTS PROPANE 2 4 SPECIFICATIONS 4005 CB 4002 CB PROPANE MODELS 3 5 MAIN COMPONENTS FOR ASSEMBLY 4 6 ASSEM...
Страница 4: ...This appliance is a transportable infrared patio deck and garden heater for operation with LPG Liquefied Petroleum Gas The 4005 CB 4002 CB burner is controlled and adjusted by the gas control knob located below the burner and the gas supply is controlled by the valve on the portable propane gas cylinder The gas supply is fed up through the inside of the pole using flexible gas hose These installat...
Страница 5: ... fully closed by turning completely clockwise 2 Open cylinder valve for Propane supply 3 Apply the soap solution generously to all connections and hoses 4 Carefully examine all connections in the gas train 5 If bubbles occur there IS a leak Close supply valve completely 6 Retighten the leaking connection and repeat leak test process until ALL leaking has ceased no matter how small the bubbles may ...
Страница 6: ...nput rating 38 000 BTUH Low fire input rating 25 000 BTUH Cylinder size 20 lb cylinder not included Cylinder connection QCC 1 Fuel consumption 20 lb cylinder 12 hours at maximum setting ambient temperature affects rate of fuel delivery Net Weight 60 lbs not including cylinder Effective radiant range 8 to 20 foot circle affected by wind and ambient temperature Certifications CSA International USA a...
Страница 7: ...ck Finish finish Model 4005 CB 4002 34 Main burner head assembly unit 32 diameter single piece aluminum reflector 34 tall cylinder housing and base Burner post support brackets 3 52 gas supply hose LPG Regulator on hose and QCC 1 fittings 4 ea M6 x 10mm machine screws for burner to upper post assembly 6 ea M6 x 35mm with nuts for post to brackets 3 ea M8 x 15mm bolts for post bracket to heater bas...
Страница 8: ... brackets to base L brackets using four 8 x 3 4 bolts and nuts Note Bolt heads face the wheel Position wheel brackets with curve up Align pairs of holes in each end of L brackets to those in opposite sides of the base fasten in place with 8 x 3 4 bolts nuts NOTE Position wheel brackets with curve up Assemble wheels to wheel brackets using axle bolts nuts Attach the 3 post mounting brackets to the ...
Страница 9: ...nder cover 3 Attach hose securely to burner 4 Allow burner to rest in post 5 Connect hose to gas cylinder 6 Lift burner and leak test all connections See section 3 1 page 2 section 5 1 next page 7 Fasten burner securely in place with four 1 2 machine screws Page 6 1 Install a washer onto threaded portion of wing bolts 2 Align holes in reflector to those in the brackets at top of burner 3 Secure re...
Страница 10: ...he leaking connection and repeat leak test process until ALL leaking has ceased no matter how small If the leak cannot be permanently repaired close the cylinder valve completely and con tact a qualified and licensed gas technician for repair parts and service After successful leak test ensure that the burner assembly and all other components are securely fastened Lift the cylinder cover up from t...
Страница 11: ...Install heater on a levelled solid and stable surface Do not install in an explosive environment Keep away from areas where gas vapours are present or inflammable liquids are stored or used In case of strong winds completely shut off the heater and the gas valve In case of very high winds remove reflector dome Do not move the heater when it is hot Do Not operate the heater when the wheels are exte...
Страница 12: ...se TO TURN OFF 1 Turn the knob clockwise until it stops 2 Depress knob and turn fully clockwise to shut of the gas supply completely Warning A 5 minute complete shut off period is required before the appliance is re lighted In very strong winds turn off the heater turn off the gas cylinder valve Allow the heater to cool down before moving to a sheltered location DO NOT move the heater while it is ...
Страница 13: ...ure is low or regulator is defective Replace empty LPG gas cylinder or defec tive regulator Check gas pressure NG Gas inlet hose is kinked or bent Spider or insect cocoon Check straighten out hose for damage Check for obstructions Burner Unit Carbon on reflector emitter screen or Thick black smoke Clean components as needed check for probable cause and rectify 10 TROUBLE SHOOTING WARNING THIS SECT...
Страница 14: ...re gas cylinder in a well ventilated area For more compact storage and to avoid damage the reflector may be removed 12 PREVENTATIVE CARE AND MAINTENANCE The burner area is likely to attract spiders especially inside orifices Once a year the heater should be inspected for spider webs insects and debris around burners and orifices Plugged injectors or orifices will obstruct the gas flow to the burne...
Страница 15: ...GP M45J CX 01A 4005 CB 4002 CB Manual RD JUN 2008 R L 02A BA Page 12 ...
Страница 16: ...ing products improperlyinstalled misused exposed to or damaged by neg ligence accident corrosive or contaminating atmosphere water excessive thermal shock impact abrasion normal wear due to use alteration or operation contraryto the owner s manual or if the serial number has been altered defaced or removed This warranty shall not apply if the input to the heating product exceeds by more than 2 of ...