to go into the submenu, as shown in Figure 4-12.
Figure 4-12 Measurement source selection Screen
Use UP and DOWN buttons to choose Input, Output, Bypass, Load, and Battery option, and press
ENTER button to go into submenu. The measurement can be read listed in Table 4-4.
Table 4-4: Measurement data
Menu
Item
Explanation
Input
L-N Voltage (V)
Input phase voltage (L1, L2, L3). Units 0.1V.
Frequency (Hz)
Input Frequency (L1, L2, L3). Units 0.1Hz.
Output
L-N Voltage (V)
Output phase voltage (L1, L2, L3). Units 0.1V.
L-N Current (A)
Output phase current (L1, L2, L3). Units 0.1A.
Frequency (Hz)
Output Frequency (L1, L2, L3). Units 0.1Hz.
Power Factor
Output Power Factor (L1, L2, L3).
Bypass
L-N Voltage (V)
Bypass phase voltage (L1, L2, L3). Units 0.1V.
Frequency (Hz)
Bypass Frequency (L1, L2, L3). Units 0.1Hz.
Power Factor
Bypass Power Factor (L1, L2, L3).
Load
Sout (KVA)
Apparent power. Units 0.1KVA.
Pout (KW)
Active power. Units 0.1KW.
Load Level (%)
The percentage of the UPS rating load. Units 1%.
Battery
Positive Voltage (V)
Battery Positive Voltage. Units 0.1V.
Negative Voltage (V)
Battery Negative Voltage. Units 0.1V.
Positive Current (A)
Battery Positive Current. Units 0.1A.
Negative Current (A) Battery Negative Current. Units 0.1A.
Remain Time (Sec)
Battery run time remaining. Units 1sec.
Capacity (%)
The percentage of the capacity of the battery. Units 1%.
Test Result
Battery test result
Charging Status
Battery charging status
Temperature1(
℃
)
Battery cabinet temperature of STS module. Units 0.1
℃
.
Temperature2(
℃
)
Battery cabinet temperature of extra communication
card T1. Units 0.1
℃
.
Temperature3(
℃
)
Battery cabinet temperature of extra communication
card T2. Units 0.1
℃
.