51
INFOSEC UPS SYSTEM – 4 rue de la Rigotière – 44700 Orvault – France – www.infosec-ups.com
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – [email protected] – 03 15 37 59 204 03
Charging current (max.)
4.0 A ± 10%
4.0 A ± 10%
4.0 A ± 10%
Charging voltage
14.4 V ± 1%
DISPLAY
LCD screen
UPS status, Load level, Battery level, Input / Output voltage,
Discharge timer and Fault conditions
ALARMS
Battery mode
Sounding every 4 seconds
Low battery
Sounding every second
Overload
Sounding twice every second
Default
Continuously sounding
Bypass mode
Sounding every 2 minutes
PHYSICAL CHARACTERISTICS
Standard model
Dimensions H x W x D (mm)
UPS: 668 x 438 x
133[3U]
Battery pack: 580 x 438
x 133[3U]
UPS: 668 x 438 x 266[6U]
Battery pack : 580 x 438 x 133[3U] x 2 pcs
Net Weight (kg)
UPS: 22
Battery pack: 63
UPS: 45
Battery pack: 63 x 2 pcs
Long-run model
(S)
Dimensions H x W x D (mm)
UPS: 870 x 580 x 250
Battery pack: 870 x 580
x 250
UPS: 870 x 580 x 381
Battery pack: 870 x 580 x 250
Net Weight (kg)
UPS: 26
Battery pack: 67
UPS: 50
Battery pack: 67 x 2 pcs
ENVIRONMENT
Humidity
<95 % RH at 0- 40°C (non condensing)
Noise level
<58dB to 1 Meter
<60dB to 1 Meter
MANAGEMENT / COMMUNICATION
RS232 & USB communications ports
Supports Windows family, Novell, Linux, Mac and FreeBSD
Optional SNMP
Power management from SNMP manager and web browser
Software
InfoPower
NORMS
Standard
CE
EMC
EN62040-2/2006
Low voltage (safety)
EN62040-1-1/2003,2006/95/EC
WARRANTY
Warranty
2 years
* Derate capacity to to 90% when the output voltage is adjusted to 208VAC.
**If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
***Product specifications are subject to change without further notice.