ETR EVO UPS User Manual (Ver. 1.0)
Page 49
7.3.2. Starting Up the UPS with External Battery
1.
Put the battery fast fuses(if exist) into the battery circuit breaker (F5). Do not close the
circuit breaker yet!
2.
Switch the input circuit breaker on the distribution panel to “ON” position.
3.
Switch the input circuit breaker (F1) to “ON” position.
4.
If exists, switch Bypass circuit breaker (F4) to “ON” position.
5.
Switch the inrush circuit breaker (F6) to “ON” position.
6.
Wait till ‘Online Operation’ shown on LCD.
7.
Switch the circuit breaker on external battery cabinet to “ON” position.
8.
Switch the battery circuit breaker on UPS (F5) to “ON” position.
9.
Switch the output circuit breaker (F2) to “ON” position.
10.
Switch the output circuit breaker on the distribution panel to “ON” position.
Afterwards UPS starts to supply the loads.
7.4. Decommissioning
Follow the order written below to decommission the UPS:
1.
Switch the output circuit breaker on the distribution panel to “OFF” position.
2.
Switch the output circuit breaker (F2) to “OFF” position.
3.
Switch battery circuit breaker (F5) to “OFF” position.
4.
If exists, external battery cabinet circuit breakers to “OFF” position.
5.
Switch the input circuit breaker on the distribution panel to “OFF” position.
6.
Switch the inrush circuit breaker (F6) to “OFF” position.
7.
Switch the input circuit breaker (F1) to “OFF” position.
8.
If exists, switch Bypass circuit breaker (F4) to “OFF” position.
9.
Wait a few minutes till UPS completely turn off.
7.5. Starting Up the UPS without Battery
It is possible to use UPS without batteries as a voltage and frequency regulator. If the UPS is used in
this feature, you must set the battery PARALLEL string number to “0” through Setting Menu. This
setup can be done by Service Password so please contact with your Authorized Technical Personnel.
If you set “BYPASS: DISABLED”and in the meantime the inverter is disabled or
blocked
because of any reason, all loads at the output would be deenergized.
Содержание ETR EVO Series
Страница 16: ...ETR EVO UPS User Manual Ver 1 0 Page 11 10 15kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 17: ...ETR EVO UPS User Manual Ver 1 0 Page 12 20 30kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 18: ...ETR EVO UPS User Manual Ver 1 0 Page 13 40 60kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 19: ...ETR EVO UPS User Manual Ver 1 0 Page 14 80kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 20: ...ETR EVO UPS User Manual Ver 1 0 Page 15 100kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 21: ...ETR EVO UPS User Manual Ver 1 0 Page 16 120kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 22: ...ETR EVO UPS User Manual Ver 1 0 Page 17 160kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 23: ...ETR EVO UPS User Manual Ver 1 0 Page 18 200kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 36: ...ETR EVO UPS User Manual Ver 1 0 Page 31...
Страница 71: ...ETR EVO UPS User Manual Ver 1 0 Page 66 40 200kVA Standard UPS 40 200kVA UPS with Split Bypass...